Telemecanique XMLR250M1P25 XMLR Series Fixed Differential, Pressure Sensor sensing, 5 to 10 ms response, Solid State/PNP output, 24 VDC

Pressure Sensors
PDW~11800659 MFG #: XMLR250M1P25
Telemecanique Sensors
345.00000 / ea
Telemecanique XMLR250M1P25, Fixed Differential, XMLR Series, Pressure Sensor Sensing Method, 5 to 10 ms Response, Solid State/PNP Output, 24 VDC, 50 mA, Male connector Connection, (1) Yellow LED Light Source, 3625.94 psi Pressure, 3.46 in H x 1.61 in W x 1.65 in D Size, IP65/IP67 Enclosure, -20 to 80 deg C Operating, Environmental Conditions: -40 to 176
QTY
  • Applications
  • Features
For local signalling, For electrical connection and G 1/4inch, For numerous industrial applications requiring display, control or regulation of pressure/vacuum levels, For pressure control or monitoring on pumps, For fluid connection, For controlling fluids such as fresh water
Polyester front material
0.5 kV DC uimp rated impulse withstand voltage
Fresh water 32 to 176 deg F (0 to 80 deg C))Air -4 to 176 deg F (-20 to 80 deg C))Hydraulic oil -4 to 176 deg F (-20 to 80 deg C))Refrigeration fluid -4 to 176 deg F (-20 to 80 deg C)) controlled fluid
290 to 3625 psi (1999.48 to 24993.49 kPa)2908 to 3625.94 psi (20 to 250 bar)2 to 25 MPa adjustable range of switching point on rising pressure
0.75 MPa109 psi (751.53 kPa)108.78 psi (7.5 bar) minimum differential travel
Polyacrylamide 316L stainless steel housing material
Any position, but disposals can falsified the measurement in case of upside down mounting operating position
Overload protection, Reverse polarity, Overvoltage protection, Short-circuit protection type
0 to 50 s in steps of 1 second switching output time delay
Fast 50 msNormal 200 msSlow 600 ms display response time type
Fast 50 msNormal 200 msSlow 600 ms display response time type
300 ms maximum delay first up
<= 1 % of the measuring range overall accuracy
<= 0.5 % of the measuring range linearity error on analogue output
<= 0.2 % of the measuring range hysteresis on analogue output
<= 0.6 % of the measuring range measurement accuracy on switching output
+/- 03 % of measuring range/ deg C drift of the sensitivity
+/- 0.1 % of measuring range/ deg C drift of the zero point
<= 1 % of the measuring range display accuracy