Telemecanique 9013GHG2J30 Pumptrol™ Electro-Mechanical Pressure Switch, 65 to 200 psi, 20 to 40 psi, 2NC DPST/DB
Pressure Control Switches
33840
MFG #: 9013GHG2J30
Telemecanique Sensors
127.47000
/ ea
Telemecanique 9013GHG2J30 PRESSURE SWITCH 575VAC 5HP G +OPTIONS,-,0.25 inch NPSF internal conforming to UL 508,20...40 psi,200 psi (40...170 psi),65...200 psi,80...100 psi,300 PSIG,40 to 170 PSIG,DPST,General Purpose (Indoor),NEMA 1,Pressure Switch,Pumptrol,Screw Clamp,UL listed, CSA,air (-22...257 deg.F)-fresh water (-22...257 deg.F),control electrically driven water pumps and air compressors
- 360 Degree View URL - 360(360 Degree View URL)
- Brochure URL - 11003_U15DY9OPJN7FG43B.pdf(Brochure URL)
- Catalog URL - IDW_DOCUMENT_b10280cf867b73e94e1871c4f71f7a065c58d3555af5a3fb8c8a52715abc2a2f.pdf(Catalog URL)
- Compliance Cert URL - Square_D_9013GHG2J30_Compliance_Certificate.pdf(Compliance Cert URL)
- Install Instructions 1 URL - 11003_BGX9OJ5D4NT2VYI1.pdf(Install Instructions 1 URL)
- Seller Home Page URL - us(Seller Home Page URL)
- Service Manual URL - 11003_CN8RVX013QY6IDJE.pdf(Service Manual URL)
- Service Manual URL - 11003_CPJTB8F0X1VINW4H.pdf(Service Manual URL)
- Spec Sheet URL - 11003_ZOQB32VP8ESW1TIX.pdf(Spec Sheet URL)
- Applications
- Features
Control electrically driven water pumps and air compressors;Power circuit;Regulation between 2 thresholds |
- |
Contacts open on pressure rise |
The class 9013 type G devices cover higher electrical ratings for direct control of motors in pump and compressor applications |
Diaphragm actuated |
2 NC, snap action, DPST-DB, form YY contact |
Air (-22 to 257 deg F), fresh water (-22 to 257 deg F) controlled fluid |
1/4 in NPSF internal conforming to UL 508 fluid connection |
Regulation between 2 thresholds, adjustable differential scale |
4 terminal blocks |
Screw clamp terminals, 10 AWG clamping capacity electrical connection |
Nitrile (Buna-N) diaphragm |
300000 cycles mechanical durability, 100000 cycles at 10 cyc/mn electrical durability |
Zinc plated steel or equivalent flange |
0.75 kW (1 hp) at 230 VDC, 3.75 kW (5 hp) at 230 VAC 3 phases, 1.5 kW (2 hp) at 115 VAC, 1 phase, 2.2 kW (3 hp) at 115 VAC 3 phases, 3.7 kW (5 hp) at 460 VAC 3 phases, 2.2 kW (3 hp) at 230 VAC, 1 phase, 0.75 kW (1 hp) at 115 VDC, 3.7 kW (5 hp) at 575 VAC, 1 phase, 3.7 kW (5 hp) at 460 VAC, 1 phase, 3.7 kW (5 hp) at 575 VAC 3-phase |
General purpose (indoor) enclosure |
Bracket mounting |
Standard action |
3 knockouts for 1/2 in conduit UL 508 cable entry |
Noryl thermoplastic resin |
General purpose (indoor) environmental conditions |