• Applications
  • Features
Process and Utilities Applications
Variable torque standard;constant torque standard;optimized torque mode;STO (safe torque off) SIL 3;16 preset speeds;Forced convection;Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16;motor screw terminal 2.5...6 mm² AWG 14...AWG 10;line side screw terminal 2.5...6 mm² AWG 14...AWG 10;1;Thermal protection motor;safe torque off motor;motor phase break motor;thermal protection drive;safe torque off drive;overheating drive;overcurrent between output phases and earth drive;overload of output voltage drive;short-circuit protection drive;motor phase break drive;overvoltages on the DC bus drive;line supply overvoltage drive;line supply undervoltage drive;line supply phase loss drive;overspeed drive;break on the control circuit drive;External supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection;internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection;internal supply for digital inputs and STO 24 V DC 21-27 V), <200 mA overload and short-circuit protection
Forced convection type cooling
4/12 kHz with derating factor switching frequency
Between power and control terminal isolation