Schneider Electric I-Line™ PowerPact™ B BDA260601 BD 060 80% Rated Molded Case Circuit Breaker, 600Y/347 VAC/250 VDC, 60 A, 25 kA at 240 VAC/18 kA at 480 VAC/14 kA at 600Y/347 VAC Interrupt, 2 Poles, Thermal/Magnetic Trip
Molded Case Circuit Breakers
1294878
MFG #: BDA260601
Square D™
515.61000
/ ea
Schneider Electric I-Line™ PowerPact™ B Molded Case Circuit Breaker, 80% Rated, Series: BD 060, 600Y/347 VAC/250 VDC, 60 A, 50/60 Hz Frequency, 25 kA at 240 VAC/18 kA at 480 VAC/14 kA at 600Y/347 VAC Interrupt, B Frame, Thermal/Magnetic Trip, 640 to 960 A Trip, 2 Pole, 1 ph, Toggle Actuator, Line/Load Lug Connection, 14 to 2/0 AWG Al/Cu Wire, NEMA AB4/IP40 Enclosure, -13 to 158 deg F, 5.39 in H x 2.12 in W x 4.01 in D Dimensions, Gray
- 360 Degree View URL - index.html?pid=11003&id=13924279360Den&ext=webp(360 Degree View URL)
- Brochure URL - 11003_9KJEVN7GRBCHIZ3Y.pdf(Brochure URL)
- Computer~Aided [CAD|BIM] Model URL - files?p_enDocType=CAD&p_File_Name=BDA260601_3D.stp(Computer~Aided [CAD|BIM] Model URL)
- Install Instructions 1 URL - files?p_File_Name=EAV91190 Rev01 2P B I-Line NA.pdf(Install Instructions 1 URL)
- Seller Home Page URL - us(Seller Home Page URL)
- Spec Sheet URL - 11003_A89JRHYUC5O67IST.pdf(Spec Sheet URL)
- Tech Drawing URL - 11003_XSEH5794VWUZ0KJN.pdf(Tech Drawing URL)
- Applications
- Features
Industrial Control Panels, Commercial OEM, Electrical Distribution Equipment, Commercial Buildings and Industrial Buildings |
Economical fixed thermal magnetic trip units from 15 to 125 A up to 600Y/347 VAC and 250 VDC |
Unit mount construction includes integrated DIN rail and traditional back pan mounting capability |
Best in class I-Line™ mounting for Square D™ panelboard and switchboard applications |
A wide range of field installable accessories for more flexibility and less inventory |
Modular, easy to install, terminal options include patented EverLink™ lugs with or without integrated control wire terminals, mechanical lugs, compression lugs, power distribution connectors and busbar connectors |
Broad offering of operating mechanisms designed to be used as the main panel disconnect for control panel applications |
25 kA at 240 VAC, 18 kA at 480 VAC, 14 kA at 600Y/347 VAC, 10 kA at 250 VDC interrupt rating |