Appleton® EFS2502023GFI U-Line® Pin and Sleeve Receptacle Assembly, 125 VAC, 20 A

Explosion Proof Pin & Sleeve Receptacles
451693 MFG #: EFS2502023GFI
Appleton™
1853.70000 / ea
  • ARRA Compliant: C
  • Buy American Compliant: N
  • Catalog Number: EFS2502023GFI
  • Country of Origin: MX
  • Currency: USD
  • EU RoHS Indicator: C
  • Gross Weight Per Pack: 9.0000 lb
  • Gross Weight per Pack Metric: 4.08
  • Gross Weight UOM Metric: kg
  • Height: 7.60 in
  • Height [Metric]: 19.3040 cm
  • Length: 9.00 in
  • Length [Metric]: 22.8600 cm
  • Material: Malleable Iron
  • Mounting: Surface Mount With 1/2 IN Dead-End Hub
  • NEMA Rating: NEMA 3/3R/7BCD/9EFG
  • Standard: Class I, Groups C and D, Class II, Groups F and G, and Class III; UL Listed: E81751; UL Standard: 943, 1203
  • Standards: ARRA CompliantRoHS CompliantClass I, Groups C and D, Class II, Groups F and G and Class IIIUL File No. E81751UL 943UL 1203
  • Sub Brand: U-Line
  • Type: 2-Gang Dead End Dust-Ignitionproof
  • UNSPSC: 39121406
  • UPC 11: 78138167116
  • UPC 12: 781381671163
  • Width: 7.60 in
  • Width [Metric]: 19.3040 cm
  • Stock Status: NONSTOCK
  • Brand: Appleton™
  • Manufacturer: Appleton
  • Amperage Rating: 20 A
  • Voltage Rating: 125 VAC
U-Line® plugs and receptacles allow the use of electrical equipment in hazardous locations. In non-hazardous locations, the U-Line ECP plug fits into standard NEMA 5-20R and 6-20R receptacles. In hazardous locations, the same U-Line plug is the key to energizing the explosionproof U-Line receptacle. Although U-Line plugs can be used with ordinary receptacles, U-Line receptacles are designed so that they cant be energized by an ordinary plug - ensuring that only safe connections can be made in a hazardous location. Its an convenient, time- and money-saving solution for handheld tools, lighting and other equipment that might be used in both ordinary and hazardous locations. When using a U-Line plug in an explosionproof U-Line receptacle, a twist of the plug makes electrical contact and locks the plug in place with an audible click. The neoprene gasket in the throat of the receptacle seals against the plug or the spring-loaded cover to seal out water, dust and corrosive compounds.
QTY
  • Features
Explosionproof, dust-ignitionproof; EFSR-GFI cover installed on two-gang EFD box together with U-Line factory sealed receptacle; Glass-filled reinforced polyester insulating blocks
Explosion proof, dust-ignition proof
Factory sealed construction; no external seals are required. Arcing is confined within the devices interior sealed chamber
EFSR-GFI cover installed on two-gang EFD box together with U-Line factory sealed receptacle
Glass-filled reinforced polyester insulating blocks
Smooth-operating test and reset buttons
Can be installed in standard EFD Series mounting boxes
Provides required ground fault protection for portable electrically-operated devices. Meets all UL and CSA requirements for ground fault protection in hazardous locations
Well suited for use in highly corrosive atmospheres and wet locations
Surface mount
1/2 in dead-end hub
2-gang
Baked gray epoxy clad