Appleton® EYSF200 Unilet® EYS Explosionproof Conduit Sealing Fitting, 2 in, For Use With IMC/Threaded Rigid Metal Conduit
Explosion Proof Conduit Sealing Fittings
17283
MFG #: EYSF200
Appleton™
116.18000
/ ea
- Application: For Use With Threaded Rigid Metal Conduit and IMC
- ARRA Compliant: N
- Buy American Compliant: N
- Catalog Number: EYSF200
- Connection: Tapered FNPT
- Country of Origin: MX
- Currency: USD
- Dimensions: 6.25 in L x 2.94 in W
- EU RoHS Indicator: C
- Gross Weight Per Pack: 2.4400 lb
- Gross Weight per Pack Metric: 1.11
- Gross Weight UOM Metric: kg
- Height: 1.50 in
- Height [Metric]: 3.8100 cm
- Length: 17.80 in
- Length [Metric]: 45.2120 cm
- Series: EYS
- Standard: UL 886 (1203), UL File Number E10444, CSA C22.2 No. 30, CSA 065181
- Standards: UL 1203 File No. E10444CSA C22.2 No. 30CSA 065181RoHS Compliant
- Sub Brand: UNILETS
- Type: Dust-Ignitionproof Explosionproof Raintight
- UNSPSC: 39121311
- UPC 11: 78138133096
- UPC 12: 781381330961
- Width: 8.50 in
- Width [Metric]: 21.5900 cm
- Stock Status: NONSTOCK
- Brand: Appleton™
- Manufacturer: Appleton
- Finish: Zinc Electroplate/Chromate/Epoxy Powder Coat
- Material: Malleable Iron
- Size: 2 in
- Suitable For Use With: IMC/Threaded Rigid Metallic Conduit
These Appleton sealing fittings minimize the passage of gases and vapors and prevent the passage of flames from one portion of a conduit system to another. They prevent pressure piling within conduit system and contain any explosion that occurs. The EYS series is used for sealing vertical conduit, and provides a large opening for damming and filling.
- Applications
- Features
For Use With Threaded Rigid Metal Conduit and IMC |
For preventing passage of gases, vapors or flames from one portion of conduit system to another; Required in Class I, Division 1 and 2 locations within 18 IN of enclosures containing apparatus that may cause arcs, sparks or high temperatures; Required in Class I, Division 1 and 2 locations where 2 IN or larger conduit enters enclosure, fitting housing terminals, splices or taps; Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location; Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 IN or less conduit, seal must be located within 18 IN of either enclosure; Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in Class I, Division 2 locations; Explosionproof, dust-ignitionproof, raintight; Smooth, rounded integral bushing in each hub protects conductor insulation; Accurately tapped, tapered threads for tight, rigid joints and ground continuity; F |
Smooth, rounded integral bushing in each hub to protect conductor insulation |
Accurately tapped, tapered NPT threads for tight, rigid joints and ground continuity |
Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub |
Large opening for damming and filling |
Restrict any explosion to the sealed off enclosure |
Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures |
Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps |
Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location |
Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure |
Required where cables which exceed rate of gas or vapor transmission permitted for seals are used in Class I, Division 2 locations |
Tapered FNPT connection |
25% fill vertical conduit sealing fittings |
Chromate/epoxy powder coated/zinc electroplated finish |
25% fill vertical conduit sealing fittings |
Triple-Coat (Zinc Electroplate, Chromate And epoxy Powder Coat) finish |