Schneider Electric LZ1H2X4BD TESYS Series, 24 VDC v coil, 3 poles, IP20 enclosure
IEC Starters
PDW~12047138
MFG #: LZ1H2X4BD
Square D™
0.00000
/ ea
- Alternate Catalog Number: LZ1H2X4BD
- ARRA Compliant: N
- Buy American Compliant: N
- Catalog Number: LZ1H2X4BD
- Connection: screw clamp terminals 1 0.2-2.5 mm² rigid; screw clamp terminals 1 0.25-2.5 mm² flexible - with cable end; screw clamp terminals 1 0.2-2.5 mm² flexible - without cable end
- Contact Configuration: 1 C/O Fault Signalling
- Country of Origin: DE
- Currency: USD
- EU RoHS Indicator: Y
- Gross Volume Per Pack: 33.84
- Gross Volume per Pack Metric: 554.54
- Gross Volume UOM: CI
- Gross Volume UOM Metric: cm3
- Gross Weight Per Pack: 2.5300 lb
- Gross Weight per Pack Metric: 253.00
- Gross Weight UOM Metric: g
- Harmonization Tariff Schedule Code: 8537106000
- Height: 3.5000 in
- Height [Metric]: 3.5000 cm
- Item Group: 22349
- Length: 12.0000 in
- Length [Metric]: 12.0000 cm
- Material Composition Declaration: https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=422433155&lang=en-us
- Mounting: DIN rail;By clips
- Number Of Poles: 3
- Returnable: N
- Size: 4.51 in
- Standard: IEC 60947-4-2;UL 60947-4-1
- Sub Brand: TeSys Hybrid;TeSys;LZ1H
- UNSPSC: 39121521
- Width: 11.7000 in
- Width [Metric]: 11.7000 cm
- Brand: Square D™
- Manufacturer: Schneider Electric
- Coil Voltage: 24 V DC;19.2...30 V DC
- Type: Ultra-compact starter
Schneider Electric LZ1H2X4BD, TESYS Series, 500 VAC, 2.4 A, 0.37 to 0.65 kW Motor, 24 VDC Coil, 3 Pole, Automatic/Electrical/Manual Reset, IP20 Enclosure, 30 cycles Operating Cycles, -13 to 158 deg F Operating, 3.90 in H x 0.89 in W x 4.51 in D Dimensions
- Brochure URL - d6eadc55f06b2daa499fb5333ff40af32203c9b9.pdf(Brochure URL)
- Computer~Aided [CAD|BIM] Model URL(Computer~Aided [CAD|BIM] Model URL)
- Service Manual URL - 11003_6BXTDSWJF8LRONE4.pdf(Service Manual URL)
- Seller Home Page URL - us(Seller Home Page URL)
- Install Instructions 1 URL - 11003_7CXKW1LJFPMD28T5.pdf(Install Instructions 1 URL)
- Service Manual URL - 11003_FY521UG8SINDTH3J.pdf(Service Manual URL)
- Spec Sheet URL - 11003_DCMG97KH4SNB5YLA.pdf(Spec Sheet URL)
- User Manual URL - 11003_YRZ3XTKD256VE98N.pdf(User Manual URL)
- User Manual URL - 11003_7A5PJVY0OECKGLZ9.pdf(User Manual URL)
- Applications
- Features
For indication of tripping and motor running, For one direction of rotation, an adjustable motor current 0, For control and power, it can be used without derating for ambient temperatures from -25 to 70, For ON/OFF motor running and remote reset after thermal tripping, 1C/O contact relay for fault, For power contacts procures ultra compactness, For control and protection of 3-phase motors up to 0 |
It helps to significantly reduce space in control cabinets by providing up to four functions within its 22.5 mm wide body: Forward running |
Reverse running |
Protection against motor overload and phase unbalance |
Safe shutdown up to SIL3/PLe (available in the Safe Torque Off variant) |
There are two variants of the TeSys H motor starter, one for standard motor starter and another Safe Torque Off motor starter as a part of safety chains |
0.18 to 2.4 A thermal protection adjustment range |
Class 10A IEC 60947-4-2 thermal overload class |
ManualAutomatic resetElectrical reset reset |
500 V AC 50/60 Hz ui rated insulation voltage |
TC protective treatment |
TC protective treatment |
With toxic heavy metal free |