Bussmann® FRS-R-60 Fusetron™ FRS-R Current Limiting Time Delay Fuse, 60 A, 600 VAC/250 VDC, 200/20 kA Interrupt, Class RK5

Class RK5 Fuses
5148 MFG #: FRS-R-60
Bussmann
30.99000 / ea
  • Alternate Catalog Number: FRS-R-60
  • Application: Ind Facilities & Factories - Facility: Safety and Security Systems
  • ARRA Compliant: C
  • Buy American Compliant: C
  • Catalog Number: FRS-R-60
  • Connection: Ferrule end x ferrule end
  • Country of Origin: MX
  • Currency: USD
  • Element: Dual
  • EU RoHS Indicator: C
  • Gross Weight Per Pack: 0.3100 lb
  • Gross Weight per Pack Metric: 1.63
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8536100040
  • Height: 2.88 in
  • Height [Metric]: 7.3152 cm
  • Length: 13.38 in
  • Length [Metric]: 33.9852 cm
  • Response Time: 10 S at 500%
  • Size: 1.06 In Diameter X 5.50 In Length
  • Standard: CE Marked
  • Standards: ARRABuy American Act CompliantUL 248-12Class RK5, Guide JDDZ, File No. E4273CSA C22.2 No. 248.12Class 1422-02, File No. 53787CE CertifiedRoHS Complaint
  • Sub Brand: Bussmann Series
  • Type: Fuse
  • UNSPSC: 39121606
  • UPC 11: 05171250839
  • UPC 12: 051712508391
  • Width: 2.88 in
  • Width [Metric]: 7.3152 cm
  • Stock Status: NORMALLY STOCKED
  • Brand: Bussmann
  • Manufacturer: Eaton
  • Amperage Rating: 60 A
  • Class: RK-5
  • Interrupt Rating: 200 kAIC at 600 Vac20 kAIC at 250 Vdc
  • Voltage Rating: 600//250 VAC//VDC
Time-delay affords the same excellent overload protection as low peak fuses of motors and other type loads and circuits having temporary inrush currents such as those caused by transformers and solenoids. (In such circuits, Limitron fuses can only provide short circuit protection). Fusetron fuses are not as Fast-Acting on short circuits as low peak fuses and therefore cannot give as high a degree of component short circuit protection. Like the low peak fuse, Fusetron fuses permit the use of smaller size and less costly switches. Fusetron fuses fit rejection type fuse holders and can also be installed in holders for Class H fuses. They can physically and electrically replace Class H, K5, and other Class RK5 fuses.
QTY
  • Applications
  • Features
Ind Facilities & Factories - Facility: Safety and Security Systems
Renewable
Without open fuse indication
Dual-element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance short circuit and overload protection
Offers a 10 sec time delay at 5 times the rated current
The time-delay feature makes it possible to use fuse amp ratings that are much smaller than those of non-time delay fuses
Provides current limitation to help protect downstream components from high fault currents
Gives motor running back-up protection to motors without extra costs