Appleton® EYSEF350 Unilet® EY Series Explosionproof Conduit Sealing Fitting, 3-1/2 in, Malleable Iron, Epoxy Powder Coated
Explosion Proof Conduit Sealing Fittings
372548
MFG #: EYSEF350
Appleton™
814.03000
/ ea
- ARRA Compliant: N
- Buy American Compliant: N
- Catalog Number: EYSEF350
- Country of Origin: MX
- Currency: USD
- Dimensions: 9-3/4 in L x 5-1/4 in W
- EU RoHS Indicator: N
- Gross Weight Per Pack: 5.2500 lb
- Gross Weight per Pack Metric: 2.38
- Gross Weight UOM Metric: kg
- Height: 5.70 in
- Height [Metric]: 14.4780 cm
- Length: 11.00 in
- Length [Metric]: 27.9400 cm
- Series: EY Series
- Standards: UL 886UL 1203 File No. E10444CSA C22.2 No. 30CSA 065181, Class I, Groups B, C, D, Class II, Groups E, F, G, Class III
- Type: Dust-Ignitionproof Explosionproof Raintight
- UNSPSC: 39121311
- UPC 11: 78138169436
- UPC 12: 781381694360
- Width: 6.00 in
- Width [Metric]: 15.2400 cm
- Stock Status: NONSTOCK
- Brand: Appleton™
- Manufacturer: Appleton
- Finish: Triple Coated
- Material: Malleable Iron
- Size: 3-1/2 in
- Suitable For Use With: IMC/Threaded Rigid Metallic Conduit
These sealing fittings minimizes the passage of gases and vapors and prevents the passage of flames from one portion of a conduit system to another. they prevent pressure piling the within conduit system and contain any explosion that occurs. The EY series is a close radius type for sealing vertical or horizontal conduit runs.
- Features
Smooth, rounded integral bushing in each hub protects conductor insulation |
Accurately tapped, tapered threads for tight, rigid joints and ground continuity |
Dust-ignition proof, raintight |
Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub |
Close radius type for sealing vertical conduit runs |
Restrict any explosion to the sealed off enclosure |
Required in class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures |
Required in class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps |
Required in class I, Division 1 and 2 locations at the boundary where conduit leaves classified location |
Required in class I, Division 1 and 2 locations where two or more enclosures are connected by 36 or less conduit, seal must be located within 18 in of either enclosure |
Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in class I, Division 2locations |
3.59 in turning radius |
Female threaded connection |
40% fill expanded fill sealing fittings for close turning radius |