Appleton® EYS10 Unilet® EYS Explosionproof Conduit Sealing Fitting, 4 in, For Use With IMC/Threaded Rigid Metal Conduit

Explosion Proof Conduit Sealing Fittings
170957 MFG #: EYS10
Appleton™
835.47000 / ea
  • Application: For Use With Threaded Rigid Metal Conduit And IMC
  • ARRA Compliant: N
  • Buy American Compliant: N
  • Catalog Number: EYS10
  • Color: Gray
  • Connection: Tapered FNPT
  • Country of Origin: MX
  • Currency: USD
  • Dimensions: 9-3/4 in L x 5-1/4 in W
  • EU RoHS Indicator: C
  • Gross Weight Per Pack: 14.9900 lb
  • Gross Weight per Pack Metric: 6.80
  • Gross Weight UOM Metric: kg
  • Height: 5.90 in
  • Height [Metric]: 14.9860 cm
  • Length: 11.50 in
  • Length [Metric]: 29.2100 cm
  • Series: EYS
  • Standard: UL 886 (1203), UL File Number E10444, CSA C22.2 No. 30, CSA 065181
  • Standards: UL 886UL 1203 File No. E10444CSA C22.2 No. 30CSA 065181RoHS Compliant
  • Sub Brand: UNILETS
  • Type: Dust-Ignitionproof Explosionproof Raintight
  • UNSPSC: 39121311
  • UPC 11: 78138162111
  • UPC 12: 781381621113
  • Width: 6.50 in
  • Width [Metric]: 16.5100 cm
  • Stock Status: NONSTOCK
  • Brand: Appleton™
  • Manufacturer: Appleton
  • Finish: Zinc Electroplate/Chromate/Epoxy Powder Coat
  • Material: Grayloy-Iron
  • Size: 4 in
  • Suitable For Use With: IMC/Threaded Rigid Metallic Conduit
These Appleton sealing fittings minimize the passage of gases and vapors and prevent the passage of flames from one portion of a conduit system to another. They prevent pressure piling the within conduit system and contain any explosion that occurs. these models in the EYS series provide a close turning radius and can be used for sealing vertical or horizontal conduit runs.
QTY
  • Applications
  • Features
For Use With Threaded Rigid Metal Conduit and IMC
For preventing passage of gases, vapors or flames from one portion of conduit system to another; Required in Class I, Division 1 and 2 locations within 18 IN of enclosures containing apparatus that may cause arcs, sparks or high temperatures; Required in Class I, Division 1 and 2 locations where 2 IN or larger conduit enters enclosure, fitting housing terminals, splices or taps; Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location; Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 IN or less conduit, seal must be located within 18 IN of either enclosure; Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in Class I, Division 2 locations; Explosionproof, dust-ignitionproof, raintight; Smooth, rounded integral bushing in each hub protects conductor insulation; Accurately tapped, tapered threads for tight, rigid joints and ground continuity; F
Smooth, rounded integral bushing in each hub protects conductor insulation
Accurately tapped, tapered threads for tight, rigid joints and ground continuity
Dust-ignition proof, raintight
Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
Close radius type for sealing vertical or horizontal conduit runs
Restrict any explosion to the sealed off enclosure
Required in class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
Required in class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
Required in class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
Required in class I, Division 1 and 2 locations where two or more enclosures are connected by 36” or less conduit, seal must be located within 18 in of either enclosure
Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in class I, Division 2locations
Tapered FNPT connection
25% fill vertical and horizontal sealing fittings for close turning radius
Triple-Coat (Zinc Electroplate, Chromate And epoxy Powder Coat) finish