Appleton® EYDEF75 Unilet® EY Series Explosionproof Conduit Sealing Fitting, 3/4 in, Malleable Iron, Tri-Coated
Explosion Proof Conduit Sealing Fittings
463111
MFG #: EYDEF75
Appleton™
140.31000
/ ea
- Application: For Use With Threaded Rigid Metal Conduit and IMC
- ARRA Compliant: N
- Buy American Compliant: N
- Catalog Number: EYDEF75
- Connection: Female Threaded
- Country of Origin: MX
- Currency: USD
- EU RoHS Indicator: N
- Gross Weight Per Pack: 2.7100 lb
- Gross Weight per Pack Metric: 1.14
- Gross Weight UOM Metric: kg
- Height: 0.92 in
- Height [Metric]: 23.3680 mm
- Length: 8.10 in
- Length [Metric]: 20.5740 cm
- Standard: UL 886 (1203), UL File Number E10444, CSA C22.2 No. 30, CSA 065181, UL Listed For Class I, Groups B, C, D; Class II, Groups E, F, G; And Class III
- Standards: UL 886 (1203), File No. E10444, CSA C22.2 No. 30, File No. 065181, Class I, Groups A, B, C, D, Class II, Groups E, F, G and Class III
- Sub Brand: UNILETS
- Type: EY Series 40 PCT Expanded Fill Vertical Drain Sealing Fitting
- UNSPSC: 39121311
- UPC 11: 78138169438
- UPC 12: 781381694384
- Width: 5.10 in
- Width [Metric]: 12.9540 cm
- Stock Status: NONSTOCK
- Brand: Appleton™
- Manufacturer: Appleton
- Finish: Zinc Electroplate/Chromate/Epoxy Powder Coat
- Material: Malleable Iron
- Size: 3/4 in
These sealing fittings minimizes the passage of gases and vapors and prevents the passage of flames from one portion of a conduit system to another. they prevent pressure piling the within conduit system and contain any explosion that occurs. The EY series is a close radius type for sealing vertical or horizontal conduit runs.
- Applications
- Features
For Use With Threaded Rigid Metal Conduit and IMC |
For preventing passage of gases, vapors or flames from one portion of conduit system to another; Required in Class I, Division 1 and 2 locations within 18 IN of enclosures containing apparatus that may cause arcs, sparks or high temperatures; Required in Class I, Division 1 and 2 locations where 2 IN or larger conduit enters enclosure, fitting housing terminals, splices or taps; Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location; Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 IN or less conduit, seal must be located within 18 IN of either enclosure; Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in Class I, Division 2 locations; Explosionproof, dust-ignitionproof, raintight; Smooth, rounded integral bushing in each hub protects conductor insulation; Accurately tapped, tapered threads for tight, rigid joints and ground continuity; A |
Smooth, rounded integral bushing in each hub protects conductor insulation |
Accurately tapped, tapered threads for tight, rigid joints and ground continuity |
Dust-ignition proof, raintight |
Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub |
Close radius type for sealing vertical conduit runs |
Restrict any explosion to the sealed off enclosure |
Required in class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures |
Required in class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps |
Required in class I, Division 1 and 2 locations at the boundary where conduit leaves classified location |
Required in class I, Division 1 and 2 locations where two or more enclosures are connected by 36 or less conduit, seal must be located within 18 in of either enclosure |
Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in class I, Division 2locations |
1.38 in turning radius |
Female threaded connection |
40% fill expanded fill sealing fittings for close turning radius |
Triple-Coat (Zinc Electroplate, Chromate And epoxy Powder Coat) finish |