Schneider Electric LR3D226, 10 A
SKUPDW~12318341
MFGR #LR3D226
$/ea
Schneider Electric LR3D226, 10 A, 400 Hz Frequency, Screw Terminal, Screw Screw, Screw Screw, IP20 Enclosure, -4 to 140 deg F, 2.60 in H x 1.77 in W x 2.76 in D Dimensions
Schneider Electric LR3D226, 10 A, 400 Hz Frequency, Screw Terminal, Screw Screw, Screw Screw, IP20 Enclosure, -4 to 140 deg F, 2.60 in H x 1.77 in W x 2.76 in D Dimensions
Catalog Number LR3D226 Country of Origin US Gross Weight Per Pack 1.5100 lb Height 4.8000 Length 8.8000 UNSPSC 39122331 Width 7.8000 Brand Square D™ Manufacturer Schneider Electric Manual and automatic reset Sealable flap Pre-wiring kit Terminal block for separate mounting Can be combined with TeSys D contactors in a 45 mm wide space up to 38A , 55 mm from 40A to 65A Connectors: spring terminal, screw clamp, EverLink terminal block Class 10 & Class 20 The TeSys LRD features an integrated manual-automatic reset button and simple installation using screw clamp terminals, spring terminal, ring terminals, or EverLink terminals TeSys LRD thermal overload relays are very reliable and cover a wide range of motor ratings up to 150 A ACDC network type ACDC network type Class 10A IEC 60947-4-1 thermal overload class 16 to 24 A thermal protection adjustment range Power circuit 600 V CSAPower circuit 600 V ULPower circuit 690 V IEC 60947-4-1 ui rated insulation voltage 1.14 +/- 06 Ir IEC 60947-4-1 tripping threshold 1.5 A 240 V AC-15 signalling circuit0.1 A 250 V DC-13 signalling circuit permissible current 6 kV uimp rated impulse withstand voltage Tripping current 130 % of Ir on two phase, the last one at 0 phase failure sensitivity -4 to 140 deg F (-20 to 60 deg C) temperature compensation
content loaded
content loaded
content loaded
content loaded
- Attributes
- Documents & Resources
- Features
- Substitute Products
| Catalog Number | LR3D226 |
| Country of Origin | US |
| Gross Weight Per Pack | 1.5100 lb |
| Height | 4.8000 |
| Length | 8.8000 |
| UNSPSC | 39122331 |
| Width | 7.8000 |
| Brand | Square D™ |
| Manufacturer | Schneider Electric |
| Manual and automatic reset |
| Sealable flap |
| Pre-wiring kit |
| Terminal block for separate mounting |
| Can be combined with TeSys D contactors in a 45 mm wide space up to 38A , 55 mm from 40A to 65A |
| Connectors: spring terminal, screw clamp, EverLink terminal block |
| Class 10 & Class 20 |
| The TeSys LRD features an integrated manual-automatic reset button and simple installation using screw clamp terminals, spring terminal, ring terminals, or EverLink terminals |
| TeSys LRD thermal overload relays are very reliable and cover a wide range of motor ratings up to 150 A |
| ACDC network type |
| ACDC network type |
| Class 10A IEC 60947-4-1 thermal overload class |
| 16 to 24 A thermal protection adjustment range |
| Power circuit 600 V CSAPower circuit 600 V ULPower circuit 690 V IEC 60947-4-1 ui rated insulation voltage |
| 1.14 +/- 06 Ir IEC 60947-4-1 tripping threshold |
| 1.5 A 240 V AC-15 signalling circuit0.1 A 250 V DC-13 signalling circuit permissible current |
| 6 kV uimp rated impulse withstand voltage |
| Tripping current 130 % of Ir on two phase, the last one at 0 phase failure sensitivity |
| -4 to 140 deg F (-20 to 60 deg C) temperature compensation |