O-Z/Gedney EYAX-75 3/4 IN HOR/VERT SEALING
Explosion Proof Conduit Sealing Fittings
499371
MFG #: EYAX75
O-Z/Gedney
30.80000
/ ea
OZ-Gedney Type EYAX Vertical/Horizontal Sealing Fitting, Size: 3/4 IN, Malleable Iron, Finish: Zinc Electroplated, Connection: Tapered FNPT, Dimensions: 1-3/4 IN Body Diameter X 4-5/16 IN Overall Length, 1-3/8 IN Turning Radius, 2.25 OZ Sealing Co
- Applications
- Features
For Rigid Conduit Or IMC |
To seal vertical or horizontal conduit runs where 40 PCT conductor fill is required; To minimize the passage of gases and vapors and prevent the passage of flames from one portion of the electrical system to another through the conduit; Explosion proof, dust-ignition proof; Use with type EYC sealing compound and type EYF fiber |
To seal vertical or horizontal conduit runs where 40 PCT conductor fill is required |
To minimize the passage of gases and vapors and prevent the passage of flames from one portion of the electrical system to another through the conduit |
Use with type EYC sealing compound and type EYF fiber |
Prevent passage of gases, vapors or flames from one portion of conduit system to another |
Restrict any explosion to the sealed off enclosure |
Prevent pressure piling within conduit system |
Required in class I, division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures |
Required in class I, division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps |
Required in class I, division 1 and 2 locations at the boundary where conduit leaves classified location |
Required in class I, division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure |
Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in class I, division 2 locations |
Smooth, rounded integral bushing in each hub to protect conductor insulation |
Accurately tapped, tapered threads for tight, rigid joints and ground continuity |
Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub |
Allow up to 40% conduit fill in compliance with the national electrical code |