Appleton® EYM200 Unilet® EY Series Explosion Proof Conduit Sealing Fitting, 2 in, For Use With IMC/Threaded Rigid Metal Conduit
Explosion Proof Conduit Sealing Fittings
16766
MFG #: APPEYM200
Appleton™
125.38000
/ ea
- http://www.appletonelec.com(Seller Home Page URL)
- https://www.appleton.emerson.com/(Seller Home Page URL)
- Seller Home Page URL - appleton(Seller Home Page URL)
- Spec Sheet 1 URL(Spec Sheet 1 URL)
- Spec Sheet URL(Spec Sheet URL)
- Warranty URL - 11043_AFRVNTEYP0B9JHS4.pdf(Warranty URL)
- Warranty URL - appleton-grp-terms-and-conditions.pdf(Warranty URL)
- Applications
- Features
For Use With Threaded Rigid Metal Conduit and IMC |
For preventing passage of gases, vapors or flames from one portion of conduit system to another; Required in Class I, Division 1 and 2 locations where 2 IN or larger conduit enters enclosure, fitting housing terminals, splices or taps; Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location; Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 IN or less conduit, seal must be located within 18 IN of either enclosure; Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in Class I, Division 2 locations; Explosionproof, dust-ignitionproof, raintight; Smooth, rounded integral bushing in each hub protects conductor insulation; Accurately tapped, tapered threads for tight, rigid joints and ground continuity; Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub; Close radius type for sealing vertical or horizontal con |
Smooth, rounded integral bushing in each hub protects conductor insulation |
Accurately tapped, tapered threads for tight, rigid joints and ground continuity |
Dust-ignition proof, raintight |
Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub |
Close radius type for sealing vertical or horizontal conduit runs |
Restrict any explosion to the sealed off enclosure |
Required in class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures |
Required in class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps |
Required in class I, Division 1 and 2 locations at the boundary where conduit leaves classified location |
Required in class I, Division 1 and 2 locations where two or more enclosures are connected by 36 or less conduit, seal must be located within 18 in of either enclosure |
Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in class I, Division 2locations |
2.31 in turning radius |
Female threaded x male threaded connection |
25% fill vertical and horizontal conduit sealing fittings for close turning radius |
Triple-Coat (Zinc Electroplate, Chromate And epoxy Powder Coat) finish |