Appleton® EYF-100 Unilet® EY Series Explosionproof Conduit Sealing Fitting, 1 in, For Use With IMC/Threaded Rigid Metal Conduit

Explosion Proof Conduit Sealing Fittings
16755 MFG #: EYF-100
Appleton™
30.38000 / ea
These sealing fittings minimizes the passage of gases and vapors and prevents the passage of flames from oneportion of a conduit system to another. they prevent pressure piling the within conduit system and contain any explosion that occurs. The EY series is a close radius type for sealing vertical or horizontal conduit runs.
QTY
  • Applications
  • Features
For Use With Threaded Rigid Metal Conduit and IMC
For preventing passage of gases, vapors or flames from one portion of conduit system to another; Required in Class I, Division 1 and 2 locations where 2 IN or larger conduit enters enclosure, fitting housing terminals, splices or taps; Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location; Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 IN or less conduit, seal must be located within 18 IN of either enclosure; Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in Class I, Division 2 locations; Explosionproof, dust-ignitionproof, raintight; Smooth, rounded integral bushing in each hub protects conductor insulation; Accurately tapped, tapered threads for tight, rigid joints and ground continuity; Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub; Close radius type for sealing vertical or horizontal con
Smooth, rounded integral bushing in each hub protects conductor insulation
Accurately tapped, tapered threads for tight, rigid joints and ground continuity
Dust-ignition proof, raintight
Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
Close radius type for sealing vertical or horizontal conduit runs
Restrict any explosion to the sealed off enclosure
Required in class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
Required in class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
Required in class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
Required in class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure
Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in class I, Division 2locations
1.38 in turning radius
Female threaded connection
25% fill vertical and horizontal conduit sealing fittings for close turning radius
Triple-Coat (Zinc Electroplate, Chromate And epoxy Powder Coat) finish