• Applications
  • Features
General Purpose Lighting
Clear Globe, Guard
60000 hr rated life eliminates the need for frequent relamping
Arrangement of heat producing components results in more efficient heat dissipation for cooler fixture operation
All threaded joints are flame-tight
Fixture housing and mounting hoods are copperfree cast aluminum with baked epoxy finish, all exposed hardware is stainless steel
Aluminum body utilizes the same Code Master HID mounting hoods, and is an easy retrofit for existing Code Master HID installations; can be pendant, ceiling, wall, or stanchion mounted
ACME double-lead threads speed installation and fixture removal from mounting hood - only half as many turns are required as for single lead threads
The threads do not stick or gall, eliminating the troublesome problems often encountered with single lead threads during fixture unit removal
Safe, easy servicing without disconnecting any wiring, wireless fixture unit easily threads off mounting hood for convenient servicing or for immediate replacement with a stand by unit
External seals are not required
Globe, driver and LED array are all field replaceable
LED arrays generate light outputs from 2,580 to 13,730 lumens (an equivalent of 70 W HID to 400 W HID lamps) providing exceptional efficacy
Suitable for use in wet locations, use of a fuse voids marine outside type (salt water) rating
Complete CodeMaster LED luminaire consists of fixture unit and a mounting hood for group B applications a group B rated mounting hood must be used
20% THD, -40 to 50 deg C ambient temperature, 75 deg C supply wire temperature
50/60 Hz frequency
Stainless steel all hardware, catch assemblies and yoke bracket, silicone gasket
Baked gray epoxy clad finish, electrostatically applied for complete uniform protection
4 kV standard surge suppression
3/4 in NPT hub
Four hubs, three close up plugs