Littelfuse® KLDR015.TXP POWR-GARD® KLDR Current Limiting Time Delay Fuse, 15 A, 600 VAC/300 VDC, 200/20 kA Interrupt, Class CC

Class CC Fuses
824160 MFG #: KLDR015.TXP
Littelfuse®
19.92000 / ea
  • Alternate Catalog Number: KLDR015.TXP
  • Application: Transformer Protection
  • ARRA Compliant: N
  • Body Size: 0.41 in Dia x 1.5 in L
  • Body Style: Cartridge
  • Buy American Compliant: N
  • Catalog Number: KLDR015.TXP
  • Country of Origin: MX
  • Currency: USD
  • EU RoHS Indicator: Y
  • Frequency Rating: CC
  • Gross Weight Per Pack: 0.2000 lb
  • Gross Weight per Pack Metric: 0.09
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8536100040
  • Indicating|Non~Indicating: Non-Indicating
  • Material: Melamine
  • Mounting Type: Holder
  • Rejection|Non~Rejection: Rejection
  • Response Time: 12 s
  • Series: KLDR
  • Short Circuit Rating: 300 VDC
  • Standard: 248-4 UL Listed, Class CC
  • Standards: RoHS CompliantUL 248-4E81895CSA LR29862PROP65: This product can expose you to chemicals including nickel, which is known to the State of California to cause cancer
  • Sub Brand: POWR-GARD KLDR Series
  • Terminal Type: Ferrule
  • Type: Class CC
  • UNSPSC: 39121627
  • UPC 11: 07945879273
  • UPC 12: 079458792737
  • Stock Status: NORMALLY STOCKED
  • Brand: Littelfuse®
  • Manufacturer: Littelfuse Inc.
  • Amperage Rating: 15 A
  • Class: CC
  • Interrupt Rating: 200/20 kA
  • Voltage Rating: 600 VAC/300 VDC A
KLDR fuses are time delay fuses designed to protect control transformers, solenoids and similar inductive componets with high magnetizing currents during the first half-cycle. they provide excellent protection of motor branch circuits containing IEC or NEMA rated motor controllers or contactors.
QTY
  • Applications
  • Features
Transformer Protection
Time-Delay
Rejection feature prevents use of fuses with lower interrupting ratings or voltage ratings when used with corresponding fuse holders
Extremely current limiting reduces damage caused by heating and magnetic effects of short circuit currents
200 kA at 600 VAC, 20 kA at 300 VDC interrupt rating
Nickel plated bronze cap
12 sec minimum and 4 min maximum at 200%, 1 hr maximum at 135%, 15 min minimum at 110%
Extremely current limiting reduces damage caused by heating and magnetic effects of short-circuit currents
200 kA at 600 VAC (RMS symmetrical) and 20 kA at 300 VDC interrupt rating