• Applications
  • Features
ABL8M
INTEGRATED FUSE (NOT INTERCHANGEABLE)
Vertical operating position
85 to 264 VAC input voltage limits, 47 to 63 Hz network frequency
<=20 A inrush current
> 0.5 cos phi
>78% efficiency, 2 W power dissipation
0.18 A at 240 VAC, 0.25 A at 100 VAC current consumption
22.2 to 28.8 V adjustable output voltage limits
+/- 3 % line and load regulation
>=10 ms at 100 VAC, >=150 ms at 230 VAC holding time
2 x 0.14 to 2 x 2.5 mm AWG 26 to AWG 14 screw type terminals input connection, connection capacity, 4 x 0.14 to 4 x 2.5 mm AWG 26 to AWG 14 screw type terminals output connection, connection capacity
6561.68 ft operating altitude
Parallel/series output coupling
Class II conforming to VDE 0106-1 overvoltage category
1 LED green output voltage status
0 to 90 % during operation, 0 to 95 % in storage relative humidity
EMC conforming to EN 55022 Class B, EMC conforming to EN 61000-6-3, EMC conforming to EN/IEC 61000-6-2, EMC conforming to EN/IEC 61204-3, safety conforming to EN/IEC 60950-1, safety conforming to SELV environmental characteristic
Against short-circuits, thermal output protection type, integrated fuse (not interchangeable) output protection type
250 mV residual ripple
35 x 15 mm symmetrical DIN rail, 35 x 7.5 mm symmetrical DIN rail, panel 2 screws, 4 mm Dia mounting support
Between input and output dielectric strength