• Features
100 mA from load voltage L+ (no load), 28 mA from maximum backplane bus 3.3 VDC
Short-circuit protection
Type (2L+) -47 V limitation of inductive shutdown voltage
6 A maximum current per module, 10 W maximum on lamp load
12 Ohm lower limit, 1 kOhm upper limit
L+ (-2, 0 V), current sourcing switch: L+ (-1, 5 V), voltage drop on current sinking switch maximum 0.5 VAC for signal "1", minimum output voltage
2 A for signal "1" rated value, 20 mA for signal "1" minimum permissible range, 2.4 A for signal "1" maximum permissible range, 0.5 mA current sourcing and current sinking switches for signal "0" maximum residual current output current
30 Hz symmetrical with maximum resistive load, 0.1 Hz symmetrical with maximum inductive load, 10 Hz symmetrical maximum on lamp load
6 A up to 40 deg C, maximum, 5 A up to 55 deg C maximum, 4 A up to 60 deg C maximum horizontal installation
4 A up to 40 deg C maximum vertical installation
500 m maximum shielded and unshielded cable length
Diagnostic functions, Wire-break, short-circuit diagnostic messages
Group error SF (red) status indicator digital output (green) diagnostics indication LED
Between the channels and backplane bus potential separation digital outputs
2545 VDC load voltage L+ against backplane bus tested