or to view stock quantity and your pricing.
Steiner serves territories in Northern Illinois, Northwest Indiana and Southern Wisconsin. Please for assistance if outside our sales territory.
Sentron™ 5SJ42208HG41 Miniature Circuit Breaker, 240 VAC/125 VDC, 20 A, 14 kA Interrupt, 2 Poles, Thermal Magnetic Trip
Custom_Product_Images_Illustration
Sentron™ 5SJ42208HG41 Miniature Circuit Breaker, 240 VAC/125 VDC, 20 A, 14 kA Interrupt, 2 Poles, Thermal Magnetic Trip
SKU401475
MFGR #5SJ42208HG41
Your Cost: $129.60/ea
List: SIEMENS 5SJ42208HG41 MCB UL489 2-POLE 20A D-TRIP TYPE HSJ
SIEMENS 5SJ42208HG41 MCB UL489 2-POLE 20A D-TRIP TYPE HSJ
Actuator Type Handle Alternate Catalog Number 5SJ4220-8HG41 Application BRANCH CIRCUIT PROTECTORS ARRA Compliant C Buy American Compliant C Catalog Number 5SJ42208HG41 Connection Identical wire screw connections on line and load side. Connection Type Line/Load/Screw Country of Origin DE Currency USD Dimensions 110 mm H x 36 mm W x 70 mm D Enclosure Type IP20 EU RoHS Indicator C Frequency Rating 50 Hz Gross Volume Per Pack 23.40 Gross Volume UOM in Gross Weight Per Pack 0.7300 lb Gross Weight per Pack Metric 0.33 Gross Weight UOM Metric kg Harmonization Tariff Schedule Code 8536200040 Height 3.2500 in Height [Metric] 8.2550 cm Length 4.5000 in Length [Metric] 11.4300 cm Material N/A Mounting Type DIN Rail Number Of Poles 2 Phase 1 Power Rating 2.2 Returnable N Standard UL 489, CSA 22.2 NO. 5-02, HACR, IEC/EN 60 898, IEC/EN 60 947-2 Standards ARRA CompliantBuy American Act CompliantRoHS CompliantCSA 22.2 No 5-02CE MarkedcULus ListedEN 60 898EN 60 947-2HACR RatedUL 489 File No. E243414 Sub Brand SENTRON Temperature Rating -25 to 55 °C Type Type HSJ UNSPSC 39121601 UPC 11 66264316806 UPC 12 662643168068 Width 1.6000 in Width [Metric] 4.0640 cm Wire Size 14 to 4 AWG Stock Status NONSTOCK Brand Siemens Manufacturer Siemens Amperage Rating 20 A Interrupt Rating 14 kA Trip Type Thermal Magnetic Voltage Rating 240 VAC BRANCH CIRCUIT PROTECTORS 2-POLE Can be used for field wiring applications, 14 to 4 AWG, copper only D-trip is designed for high inrush loads, magnetic trip point is 10 to 20 times the MCB rating 0.75 to 35 sq-mm solid and stranded conductors Visible indicator for ON and OFF/trip Touch protection to EN50274 Identical wire screw connections on line and load side Smaller size than traditional MCCBs 35 mm DIN rail mounting
content loaded
content loaded
content loaded
content loaded
content loaded
- Attributes
- Documents & Resources
- Applications
- Features
- Substitute Products
Actuator Type | Handle |
Alternate Catalog Number | 5SJ4220-8HG41 |
Application | BRANCH CIRCUIT PROTECTORS |
ARRA Compliant | C |
Buy American Compliant | C |
Catalog Number | 5SJ42208HG41 |
Connection | Identical wire screw connections on line and load side. |
Connection Type | Line/Load/Screw |
Country of Origin | DE |
Currency | USD |
Dimensions | 110 mm H x 36 mm W x 70 mm D |
Enclosure Type | IP20 |
EU RoHS Indicator | C |
Frequency Rating | 50 Hz |
Gross Volume Per Pack | 23.40 |
Gross Volume UOM | in |
Gross Weight Per Pack | 0.7300 lb |
Gross Weight per Pack Metric | 0.33 |
Gross Weight UOM Metric | kg |
Harmonization Tariff Schedule Code | 8536200040 |
Height | 3.2500 in |
Height [Metric] | 8.2550 cm |
Length | 4.5000 in |
Length [Metric] | 11.4300 cm |
Material | N/A |
Mounting Type | DIN Rail |
Number Of Poles | 2 |
Phase | 1 |
Power Rating | 2.2 |
Returnable | N |
Standard | UL 489, CSA 22.2 NO. 5-02, HACR, IEC/EN 60 898, IEC/EN 60 947-2 |
Standards | ARRA CompliantBuy American Act CompliantRoHS CompliantCSA 22.2 No 5-02CE MarkedcULus ListedEN 60 898EN 60 947-2HACR RatedUL 489 File No. E243414 |
Sub Brand | SENTRON |
Temperature Rating | -25 to 55 °C |
Type | Type HSJ |
UNSPSC | 39121601 |
UPC 11 | 66264316806 |
UPC 12 | 662643168068 |
Width | 1.6000 in |
Width [Metric] | 4.0640 cm |
Wire Size | 14 to 4 AWG |
Stock Status | NONSTOCK |
Brand | Siemens |
Manufacturer | Siemens |
Amperage Rating | 20 A |
Interrupt Rating | 14 kA |
Trip Type | Thermal Magnetic |
Voltage Rating | 240 VAC |
BRANCH CIRCUIT PROTECTORS |
2-POLE |
Can be used for field wiring applications, 14 to 4 AWG, copper only |
D-trip is designed for high inrush loads, magnetic trip point is 10 to 20 times the MCB rating |
0.75 to 35 sq-mm solid and stranded conductors |
Visible indicator for ON and OFF/trip |
Touch protection to EN50274 |
Identical wire screw connections on line and load side |
Smaller size than traditional MCCBs |
35 mm DIN rail mounting |