Features: Wire Range: Line Side: (2) 500 KCMIL - 4 AWG; Load Side: (2) 500 KCMIL - 4 AWG; Electrical Ratings: 760 AMP Copper Wire, 620 AMP Aluminum Wire (Based On NEC Table 310-16, 75 ° C Columns); 600 Volts AC/DC (UL 1059 Class C, User Group - General Industrial); Factory And Field Wiring; Mechanical Ratings: Maximum Insulator Base Temperature: 150 ° C (302 ° F) UL RTI; Storage And Transportation Temperature Range: -35 ° C To 125 ° C (-31 ° F To 257 ° F); Flammability Rating Of Insulator Base: UL 94 V-0; Use Outside These Ratings Needs To Be Judged In The End-Use Application; Materials: Connector: High Conductive Aluminum, Tin Plated; Insulator Base: Phenolic; Terminal Set Screws: Aluminum, Tin Plated; Connector Mounting Screw: Steel, Zinc Plated; Agency Approvals: UL Recognized, UL 1059 Terminal Block Standard, File No. XCFR2.E62806; CSA Certified |