The 920 Series Ground Resistance Tester from IDEAL enables electricians to test grounding systems without disconnecting the ground, saving both time and effort. By simply clamping around the grounding rod or ground conductor, it provides direct measurements of both ground resistance and ground leakage current. For the safest, quickest and most accurate means of grounding measurement, the 920 Series from IDEAL is the answer.
- Brochure URL - 11020_61-920_manual_v4.pdf(Brochure URL)
- Catalog URL - IDW_DOCUMENT_e1d9aa38f46d9994d54b47936117c5a308037ce12a5e722bbdbb4c49e8676a3b.pdf(Catalog URL)
- http://www.idealindustries.com(Seller Home Page URL)
- Material Composition - US_ROHS_COMPLIANCE_STATEMENT_REV_2_23_2015.PDF(Material Composition)
- Compliance Cert URL - IDEAL_84_018_Compliance_Certificate.pdf(Compliance Cert URL)
- Owners Manual URL - IDEAL_61_920_Manual.pdf(Owners Manual URL)
- ROHS Compliance URL(ROHS Compliance URL)
- Spec Sheet URL - prodDetail.do?prodId=61-920(Spec Sheet URL)
- Features
Features: Larger Clamp Size 1.25 IN; Backlight; Ground Resistance 0.1 To 1200 OHM; Ground Leakage Current To 30A; Ground Continuity Loop Test; Audible Alarm; Data Storage; Data Hold; Calibration Loop Included; Resistance Accuracy: 1.5 PCT; Leakage Current Accuracy: 2.0 PCT; Auto-Power Off; Auto Ranging; Cat III - 300V; 2-Year Warranty; Carrying Case Included; Saves Up To 99 Measurements; Includes: Calibration loop, Carrying case; Warranty: 2 year |
Dual backlit display |
Self powered - no need for hand crank |
Ground leakage current to 30 A, ground continuity loop test, audible alarm, data storage, data hold |
Auto-power off, auto ranging |
Turns power off after 10 minutes of non-use |
(4) batteries AA power supply, IP40 IP, AC5320 Vrms/5 seconds withstand voltage, 50 MOhm or more at 1000 V insulation resistance |
AC current 100 mA, 0.1 mA resolution at +/-2% +/-0.7 mA, (1000 mA, 1 mA resolution, 10A, 0.01 A resolution, 30 A, 0.1 A resolution) at +/-2% accuracy |
Resistance 20 Ohm, 0.01 Ohm resolution at +/-(1.5% +/-0.05 Ohm) accuracy, 200 Ohm, 0.1 Ohm resolution at +/-(2% +/-0.5 Ohm), +/-(3% +/-2 Ohm) accuracy, 1200 Ohm, 1 Ohm-10 Ohm resolution at (+/-5% +/-5 Ohm), +/-(10% +/-10 Ohm) accuracy earth resistance auto ranging |