3M™ RJS Rejacketing Sleeve, 1 ft L Linear, Rubber, Dark Gray

Terminal Insulation Boots & Sleeves
776145 MFG #: 7100035795
3M™
227.39000 / ea
3M RJS Series Rejacketing Sleeves are designed so that 3M Cold Shrink QTII and QTIII Silicone Rubber Termination applications can be used on 3/C (three conductor) medium voltage shielded power cables of tape shield, wire shield, armored and non-armored configurations. RJS Rejacketing Assemblies are a series of silicone rubber insulators incorporating an inner expandable polyester braid designed to reduce sliding friction and deliver the insulator onto the cable. Rejacketing sleeves are designed to protect the phase legs (core) of 3/C shielded power cable from exposure to moisture, corrosion, ozone, ultra-violet radiation, physical contact and other hazards that are associated with termination operating environments. Rejacketing sleeves are designed to be used in conjunction with 3M Cold Shrink Breakout Boots and Silicone Rubber Terminations.
QTY
  • Applications
  • Features
Protect shielded phase legs after jacket has been removed in preparation for terminating
Versatile installs quickly and accommodates a wide range of cable sizes
Simple hand application no need for special installation tools
No torches or heat required
Excellent resistance to ozone and ultra-violet radiation
Good solvent resistance compatible with industry approved cable cleaners
Excellent thermal stability
High dry and wet insulation resistance
Excellent shelf life
Easy to adjust sleeve length adapts to variable equipment connection and mounting requirements
Used to protect shielded phase legs (cores) of 3/C medium voltage (35 kV and less) power cables after the jacket has been removed in preparation for terminating
Accommodate cable sizes ranging from 8 AWG (8 mm2) at 3.3 kV - 750 kcmil (325 mm2) at 35 kV
Available in six sizes to cover cable metallic shield dia ranging from 0.43 in (10.9 mm) to 1.91 in (48.5 mm)
RJS Series sleeve assemblies can be field tested using normal cable testing procedures
Rejacketing sleeves are designed to protect the phase legs (core) of 3/C shielded power cable from exposure to moisture, corrosion, ozone, ultra-violet radiation, physical contact and other hazards that are associated with termination operating environments
Cold Shrink QT-III and Q-TIII silicone rubber terminations can be used on 3/C (three conductor) medium voltage shielded power cables of tape shield, wire shield, armored and non-armored configuration