1 EYS SEALING UNILET-FEMALE

Explosion Proof Conduit Sealing Fittings
559651 MFG #: EYS36
Appleton™
48.25000 / ea
These Appleton sealing fittings minimize the passage of gases and vapors and prevent the passage of flames from one portion of a conduit system to another. they prevent pressure piling the within conduit system and contain any explosion that occurs. these models in the EYS series provide a close turning radius and can be used for sealing vertical conduit runs.
QTY
  • Applications
  • Features
For Use With Threaded Rigid Metal Conduit and IMC
For preventing passage of gases, vapors or flames from one portion of conduit system to another; Required in Class I, Division 1 and 2 locations within 18 IN of enclosures containing apparatus that may cause arcs, sparks or high temperatures; Required in Class I, Division 1 and 2 locations where 2 IN or larger conduit enters enclosure, fitting housing terminals, splices or taps; Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location; Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 IN or less conduit, seal must be located within 18 IN of either enclosure; Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in Class I, Division 2 locations; Explosionproof, dust-ignitionproof, raintight; Smooth, rounded integral bushing in each hub protects conductor insulation; Accurately tapped, tapered threads for tight, rigid joints and ground continuity; F
Smooth, rounded integral bushing in each hub to protect conductor insulation
Accurately tapped, tapered NPT threads for tight, rigid joints and ground continuity
Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
Large opening for damming and filling
Restrict any explosion to the sealed off enclosure
Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure
Required where cables which exceed rate of gas or vapor transmission permitted for seals are used in Class I, Division 2 locations
Tapered FNPT connection
25% fill vertical sealing fittings for close turning radius
Chromate/epoxy powder coated/zinc electroplated finish
25% fill vertical sealing fittings for close turning radius
Triple-Coat (Zinc Electroplate, Chromate And epoxy Powder Coat) finish