Raychem® AMC-F5 Ambient Sensing Mechanical Thermostat, SPST, Pigtail Terminal Designations

Heat Trace Thermostats
143670 MFG #: AMC-F5
nVent RAYCHEM
207.76000 / ft
  • Application: For Controlling Freeze Protection Heat-Tracing Circuits In Ordinary Areas
  • Catalog Number: AMC-F5
  • Country of Origin: US
  • Finish: Black
  • Gross Weight Per Pack: 1 lb
  • Outside Depth: 2-1/2
  • Outside Height: 5.2 in
  • Outside Width: 3.2
  • Standards: UL Listed, CSA Certified
  • Sub Brand: DigiTrace
  • UNSPSC: 41112209
  • UPC 11: 71562977065
  • UPC 12: 71562977065
  • Stock Status: NONSTOCK
  • Brand: nVent RAYCHEM
  • Manufacturer: nVent
  • Amperage Rating: 22 A
  • Poles: 1
  • Type: Fixed Set-Point Freeze-Protection Non Programmable Thermostat
The Raychem AMC-F5 thermostat is designed to control electric heat tracing systems used for pipe freeze protection in non hazardous locations. The thermostat has a fixed set point of 40 deg F (4.4 deg C) and can be used in ambient-sensing mode (with sensor in air) or line-sensing mode (with sensor placed on pipe or tank wall). It can be used to control a single heat tracing circuit or as a pilot control of a contactor switching multiple heat tracing circuits. It can also be used to control a contactor coil. Images shown for wire are for illustrative purposes only. Color shade and packaging/spooling may vary.
QTY
  • Applications
  • Features
For Controlling Freeze Protection Heat-Tracing Circuits In Ordinary Areas
The digitrace thermostat is designed to control electric heat tracing systems used for pipe freeze protection in non hazardous locations ; The thermostat has a fixed set point of 40 &176; Fand can be used in ambient-sensing mode (with sensor in air) or line-sensing mode (with sensor placed on pipe or tank wall) ; It can be used to control a single heat tracing circuit or as a pilot control of a contactor switching multiple heat tracing circuits ; It can also be used to control a contactor coil ; Enclosure: NEMA 4X, UV-resistant thermoplastics ; Entries: one 3/4 IN through hole ; Sensor exposure limits: - 30 &176; Fto 140 &176; F(- 34 ° C to 60 ° C) ; Housing exposure limits: - 30 &176; Fto 140 &176; F(- 34 ° C to 60 ° C) ; Switch: SPST ; Accuracy: +/- 3 &176; F(+/- 1.7 ° C) ; Deadband: 2 &176; Fto 12 &176; F(1.1 ° C to 6.7 ° C) above actuation temperature ;
Tin-plated copper sensor material
40 deg F nonadjustable set point
+/- 3 deg F accuracy
UV-resistant thermoplastic enclosure
2 to 12 deg F above actuation temperature dead band
- 30 to 140 deg F sensor exposure limit
- 30 to 140 deg F housing exposure limit