Edison 15.5CAVH1E CAVH Current Limiting Potential Transformer Fuse, 1 A, 15500 VAC, 80 kA Interrupt, Class E

Medium Voltage Fuse
656051 MFG #: 15.5CAVH1E
Bussmann
639.08000 / ea
  • Alternate Catalog Number: 15.5CAVH1E
  • Amperage Rating: 1 A
  • Application: Utility - Substations, Utility Transmission and DistributionUtility
  • ARRA Compliant: C
  • Body Size: 1.63 in Dia x 12.87 in L
  • Buy American Compliant: C
  • Catalog Number: 15.5CAVH1E
  • Class: Class back-up
  • Connection: Ferrule end x ferrule end
  • Country of Origin: IN
  • Currency: USD
  • EU RoHS Indicator: C
  • Gross Weight Per Pack: 2.3149 lb
  • Gross Weight per Pack Metric: 5.30
  • Harmonization Tariff Schedule Code: 8536100040
  • Height: 1.61 in
  • Height [Metric]: 4.1001 cm
  • Indicating|Non~Indicating: Indicating
  • Interrupt Rating: 80 kAIC kA
  • Length: 12.91 in
  • Length [Metric]: 32.8000 cm
  • Mounting: Bolt-on
  • Mounting Type: Bolt-On
  • Response Time: 1E
  • Series: CAVH
  • Size: 1.63 In Diameter X 12.87 In Length
  • Standard: Contact factory
  • Standards: ARRA CompliantBuy American Act CompliantRoHS CompliantBS2692-1IEC60282-1
  • Sub Brand: Bussmann Series
  • Terminal Type: Ferrule
  • Type: Medium voltage auxiliary fuse
  • UNSPSC: 39121626
  • UPC 11: 05171283116
  • UPC 12: 051712831161
  • Voltage Rating: 15,500 V
  • Width: 1.61 In
  • Width [Metric]: 4.1001 cm
  • Stock Status: NONSTOCK
  • Brand: Bussmann
  • Manufacturer: Eaton
Edison Potential Transformer Fuse, Current Limiting, Series: CAVH, Indicating/Non-Indicating: Indicating, 1 A, 15500 VAC, 80 kA Interrupt, Class: E, Ferrule Terminal, Bolt-On Mount, 1.63 in Dia x 12.87 in L Body Size
QTY
  • Applications
  • Features
Utility - Substations, Utility Transmission and DistributionUtility
Low amp, current limiting e-rated PT medium voltage fuses are general purpose fuses defined by their melting time current characteristic that permit their electrical interchangeability with other fuses of the same E-rating
E-rated general purpose fuses must have a current responsive element that will melt in 300 sec at an rms current within the range of 200% to 240% of the fuses nameplate current rating, fuse refill or link per ANSI C37.46 for fuses rated 100E or less
PT fuses are physically dimensioned for easy installation in existing hardware
Space saving size eases design considerations for new installations
Current limiting fuses provide positive interruption even on low fault currents
The fuse limits the magnitude of electromechanical stresses in the protected apparatus
These fuses are in a self-contained, non-venting package for installation indoors or outdoors in an enclosure
Open fuse indicator speeds troubleshooting by providing a positive visual indication of fuse operation
Fitted with a striker pin for indication