Bussmann® KRP-C-4000SP Low-Peak™ KRP-C Current Limiting Time Delay Fuse, 4000 A, 600 VAC, 300 kA Interrupt, Class L, Cartridge Body

Class L Fuses
44258 MFG #: KRP-C-4000SP
Bussmann
2520.41000 / ea
  • Alternate Catalog Number: KRP-C-4000SP
  • Application: Ind Facilities & Factories - Facility: Safety and Security Systems
  • ARRA Compliant: C
  • Buy American Compliant: C
  • Catalog Number: KRP-C-4000SP
  • Connection: Bolted Blade End X Bolted Blade End
  • Country of Origin: MX
  • Currency: USD
  • EU RoHS Indicator: C
  • Gross Weight Per Pack: 22.1500 lb
  • Gross Weight per Pack Metric: 10.05
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8536100040
  • Height: 6.40 in
  • Height [Metric]: 16.2560 cm
  • Length: 12.10 in
  • Length [Metric]: 30.7340 cm
  • Material: Melamine glass tube
  • Response Time: 4 sec at 500%
  • Size: 5.75 In Diameter X 10.75 In Length
  • Standard: CE Marked,RoHS Compliant
  • Standards: UL Guide No. JDDZ, File No. E4273, CSA Class 1422-02, File No. 53787, Class L per CSA C22.2, No. 248.10, CE Certified, RoHS compliant
  • Sub Brand: Bussmann Series
  • Type: Fuse
  • UNSPSC: 39121626
  • UPC 11: 05171260540
  • UPC 12: 051712605403
  • Width: 6.40 in
  • Width [Metric]: 16.2560 cm
  • Stock Status: NONSTOCK
  • Brand: Bussmann
  • Manufacturer: Eaton
  • Amperage Rating: 4000 A
  • Class: L
  • Interrupt Rating: 300 kAIC at 600 Vac
  • Voltage Rating: 600 V
Eaton's Bussmann series low peak ultimate protection fuses are the industry's only UL® Listed and CSA Certified fuses with a 300kA interrupting rating, providing 50% more protection than any other listed fuse*. The high interrupting rating allows for simple, worry-free installation in virtually any application. low peak fuses are available in Class CC, CF, J, L and RK1, so there is a fuse to meet the vast majority of 600V over current protection needs. Plus, when upgrading to low peak fuses, existing fuse inventory can be reduced by up to fuse.
QTY
  • Applications
  • Features
Ind Facilities & Factories - Facility: Safety and Security Systems
Silver Plated End Bell
Fast short circuit protection with time-delay performance provide ultimate protection
Consistent 2: 1 ampacity ratios for all low peak fuses make selective coordination easy
Current-limiting action of the fuse generally affords considerable reduction in bus bracing
All purpose silver-linked fuse for both overload and short circuit protection for high capacity systems
O-ring seals maximize pressure build-up during current-limiting action and ensure filter retention
High-grade silica sand filler accelerates response of fuse to short circuits by having quenching effect on the fuse arc
99.9 percent pure silver links provide low watt loss with low operating temperature on normal current levels and minimizes total clearing IT fault energy left-through
300 kA (RMS symmetrical) at 600 VAC interrupt rating