MFGR #9080LBA265208
Your Cost: $213.93/ea
List: Square D 9080LBA265208 POWER DISTRIBUTION BLOCK 600V 760A,(2)#4 to 500 AWG/kcmil (8)#14 to #2/0 AWG,2-Pole,600 V AC,760A 620A,9080LB,9080LB52,General Purpose Phenolic,Lugs Tin Plated Aluminum,Power Distribution Block
Square D 9080LBA265208 POWER DISTRIBUTION BLOCK 600V 760A,(2)#4 to 500 AWG/kcmil (8)#14 to #2/0 AWG,2-Pole,600 V AC,760A 620A,9080LB,9080LB52,General Purpose Phenolic,Lugs Tin Plated Aluminum,Power Distribution Block
Alternate Catalog Number 9080LBA265208 Application 9080LB,9080LB52 ARRA Compliant N Buy American Compliant N Catalog Number 9080LBA265208 Connection Tin plated aluminium lugs;Load lug 40 lbf.in AWG 8 copper or aluminium;load lug 120 lbf.in AWG 6...AWG 2/0 copper or aluminium;load lug 35 lbf.in AWG 14...AWG 10 copper or aluminium;line lug 375 lbf.in AWG 4...500 kcmil copper or aluminium A Country of Origin FR Currency USD Dimensions 5.5 in H x 5.88 in W x 3.12 in D EU RoHS Indicator Y Gross Volume Per Pack 179.52 Gross Volume per Pack Metric 2941.79 Gross Volume UOM CI Gross Volume UOM Metric cm3 Gross Weight Per Pack 2.6500 lb Gross Weight per Pack Metric 1.20 Gross Weight UOM Metric kg Harmonization Tariff Schedule Code 8536904000 Height 8.6360 in Height [Metric] 8.6360 cm Item Group 21711 Length 22.3520 in Length [Metric] 22.3520 cm Material Composition Declaration https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=372975&lang=en-us Mounting SURFACE MOUNT Returnable Y Size 3.13 IN,5.5 IN,5.88 IN VAC//VDC Standard CSA FILE 70361 CLASS 6228 01-UL RECOGNIZED E60616 CCN XCFR2-CE Substitute Product Catalog Number 9080LB52 Type 9080LB52,POWER DISTRIBUTION BLOCK UNSPSC 39121410 UPC 11 78590115707 UPC 12 785901157076 Warranty Description Contractual Warranty:18 months Width 15.2400 in Width [Metric] 15.2400 cm Stock Status NONSTOCK Brand Square D™ Manufacturer Schneider Electric Amperage Rating 760-760 A COPPER-620-620 A ALUMINIUM VAC Material PHENOLIC BLOCK Voltage Rating 600 VAC//VDC Wire Size LINE 2 , AWG 4...500 KCMIL, COPPER OR ALUMINIUM-LOAD 8 , AWG 14...AWG 2/0, COPPER OR ALUMINIUM 9080LB,9080LB52 LUGS TIN PLATED ALUMINIUM,PHENOLIC BLOCK C service class, UL94V-0 flammability rating 8 branch, 2 main terminal 10-cables 42.4 N-m tightening torque -40 to 302 deg F temperature rating 4 AWG to 500 kcmil aluminum or copper main, 14 to 2/0 AWG aluminum or copper branch wire 760 A CU, 620 A AL amperage rating
content loaded
content loaded
content loaded
content loaded
content loaded
- Attributes
- Documents & Resources
- Applications
- Features
- Substitute Products
| Alternate Catalog Number | 9080LBA265208 |
| Application | 9080LB,9080LB52 |
| ARRA Compliant | N |
| Buy American Compliant | N |
| Catalog Number | 9080LBA265208 |
| Connection | Tin plated aluminium lugs;Load lug 40 lbf.in AWG 8 copper or aluminium;load lug 120 lbf.in AWG 6...AWG 2/0 copper or aluminium;load lug 35 lbf.in AWG 14...AWG 10 copper or aluminium;line lug 375 lbf.in AWG 4...500 kcmil copper or aluminium A |
| Country of Origin | FR |
| Currency | USD |
| Dimensions | 5.5 in H x 5.88 in W x 3.12 in D |
| EU RoHS Indicator | Y |
| Gross Volume Per Pack | 179.52 |
| Gross Volume per Pack Metric | 2941.79 |
| Gross Volume UOM | CI |
| Gross Volume UOM Metric | cm3 |
| Gross Weight Per Pack | 2.6500 lb |
| Gross Weight per Pack Metric | 1.20 |
| Gross Weight UOM Metric | kg |
| Harmonization Tariff Schedule Code | 8536904000 |
| Height | 8.6360 in |
| Height [Metric] | 8.6360 cm |
| Item Group | 21711 |
| Length | 22.3520 in |
| Length [Metric] | 22.3520 cm |
| Material Composition Declaration | https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=372975&lang=en-us |
| Mounting | SURFACE MOUNT |
| Returnable | Y |
| Size | 3.13 IN,5.5 IN,5.88 IN VAC//VDC |
| Standard | CSA FILE 70361 CLASS 6228 01-UL RECOGNIZED E60616 CCN XCFR2-CE |
| Substitute Product Catalog Number | 9080LB52 |
| Type | 9080LB52,POWER DISTRIBUTION BLOCK |
| UNSPSC | 39121410 |
| UPC 11 | 78590115707 |
| UPC 12 | 785901157076 |
| Warranty Description | Contractual Warranty:18 months |
| Width | 15.2400 in |
| Width [Metric] | 15.2400 cm |
| Stock Status | NONSTOCK |
| Brand | Square D™ |
| Manufacturer | Schneider Electric |
| Amperage Rating | 760-760 A COPPER-620-620 A ALUMINIUM VAC |
| Material | PHENOLIC BLOCK |
| Voltage Rating | 600 VAC//VDC |
| Wire Size | LINE 2 , AWG 4...500 KCMIL, COPPER OR ALUMINIUM-LOAD 8 , AWG 14...AWG 2/0, COPPER OR ALUMINIUM |
| 9080LB,9080LB52 |
| LUGS TIN PLATED ALUMINIUM,PHENOLIC BLOCK |
| C service class, UL94V-0 flammability rating |
| 8 branch, 2 main terminal |
| 10-cables |
| 42.4 N-m tightening torque |
| -40 to 302 deg F temperature rating |
| 4 AWG to 500 kcmil aluminum or copper main, 14 to 2/0 AWG aluminum or copper branch wire |
| 760 A CU, 620 A AL amperage rating |