Edison Magnum® 16377-3 Barrier Terminal Power Distribution Block, 600 VAC/VDC, 570 A, 3 Poles, 4 AWG to 300 kcmil Wire

Multi Pole Distribution Blocks
656457 MFG #: 16377-3
Bussmann
343.06000 / ea
  • Alternate Catalog Number: 16377-3
  • Application: Elec Assemblies, Panels & EOEM - Electrical Assemblies, Panels and EOEMs
  • ARRA Compliant: C
  • Buy American Compliant: C
  • Catalog Number: 16377-3
  • Color: Black
  • Country of Origin: MX
  • Currency: USD
  • Dimensions: 5.21 in L x 4 in W x 3.32 in H
  • EU RoHS Indicator: C
  • Finish: Tin Plated
  • Gross Weight Per Pack: 2.2500 lb
  • Gross Weight per Pack Metric: 1.06
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8536904000
  • Height: 3.75 in
  • Height [Metric]: 9.5250 cm
  • Length: 6.50 in
  • Length [Metric]: 16.5100 cm
  • Series: 163
  • Short Circuit Current Rating: 10
  • Size: 5.21 In Length X 4.00 In Width X 3.32 In Height
  • Standard: Contact Manufacturer,Contact factory,RoHS Compliant
  • Standards: ARRA CompliantBuy American Act CompliantRoHS CompliantUL 1059508AFile No. E221592Guide XCFR2CSA Class 6228-01File No. 53787CE CertifiedUL 94-V-0 Flammability Rating
  • Sub Brand: Bussmann Series
  • Type: Power distribution block
  • UNSPSC: 39121629
  • UPC 11: 05171255643
  • UPC 12: 051712556439
  • Width: 4.25 in
  • Width [Metric]: 10.7950 cm
  • Stock Status: NONSTOCK
  • Brand: Bussmann
  • Manufacturer: Eaton
  • Amperage Rating: 570 A
  • Material: Aluminum/Tin/Thermoplastic
  • Voltage Rating: 600 VAC//VDC
  • Wire Size: 4 AWG to 300 kcmil
  • Number Of Poles: 3
Edison series UL Recognized power distribution blocks offer a variety of lineside and loadside port configurations to provide greater flexibility in panel wiring and wire management. These blocks are UL Recognized to UL 1059 and rated for use in UL 508A industrial control panels. Blocks are factory configured in 1-, 2 and 3-pole versions, and have optional covers to enhance safety (order covers separately).
QTY
  • Applications
  • Features
Elec Assemblies, Panels & EOEM - Electrical Assemblies, Panels and EOEMs
Short Circuit Current Rating 10 kA
4 AWG to 300 kcmil copper/aluminum line, 14 to 4 AWG copper, 12 to 4 AWG aluminum load connection
Dual wire applications are only viable when using two wires of the same size, stranding and insulating and conductor material in the same port
Ferrule applications allow for the use of a broader range of conductor stranding and simulate a more efficient, solid wire connection with the terminal port
Molded thermoplastic base, tin plated aluminum connector
SMD/SMT style mounting
(2) 4 AWG to 300 kcmil copper/aluminum line, (12) 14 to 4 AWG copper, 12 to 4 AWG aluminum load wire
(12) 1/4 in quick connect
(1) screw primary, (12) quick connect secondary