or to view stock quantity and your pricing.
Steiner serves territories in Northern Illinois, Northwest Indiana and Southern Wisconsin. Please for assistance if outside our sales territory.
Siemens 3RV20111DA25 3RV2 Motor Protection Circuit Breaker With 1NO-1NC Transverse Auxiliary Switch, 690 VAC, 2.2 to 3.2 A, 3 Poles
Custom_Product_Images_Illustration
Siemens 3RV20111DA25 3RV2 Motor Protection Circuit Breaker With 1NO-1NC Transverse Auxiliary Switch, 690 VAC, 2.2 to 3.2 A, 3 Poles
SKU978191
MFGR #3RV20111DA25
Your Cost: $174.00/ea
List: The SIRIUS 3RV2 motor starter protectors/circuit breakers are compact, current limiting motor starter protectors/circuit breakers which are optimized for load feeders. The motor starter protectors/circuit breakers are used for switching and protecting three-phase motors of up to 55/45 kW at 400 VAC and for other loads with rated currents of up to 100 A.
The SIRIUS 3RV2 motor starter protectors/circuit breakers are compact, current limiting motor starter protectors/circuit breakers which are optimized for load feeders. The motor starter protectors/circuit breakers are used for switching and protecting three-phase motors of up to 55/45 kW at 400 VAC and for other loads with rated currents of up to 100 A.
Alternate Catalog Number 3RV2011-1DA25 Application Used as Manual Motor Controller and in Group Installation ARRA Compliant C Auxiliary Contact Rating 1NO-1NC Buy American Compliant C Catalog Number 3RV20111DA25 Connection spring-loaded terminals Connection Type Spring Country of Origin DE Currency USD Dimensions 106 mm H x 45 mm W x 97 mm D Enclosure Type IP20 Environmental Conditions 80 -50 C EU RoHS Indicator C Frame S00 Frequency Rating 50/60 Hz Gross Volume Per Pack 40.54 Gross Volume UOM in Gross Weight Per Pack 0.8140 lb Gross Weight per Pack Metric 0.37 Gross Weight UOM Metric kg Harmonization Tariff Schedule Code 8536304000 Height 4.1800 in Height [Metric] 10.6172 cm Length 4.7300 in Length [Metric] 12.0142 cm Mounting Type DIN Rail/Snap-On/Threaded Number Of Poles 3 Operating Temperature 60 to -20 °C Phase 3 Power Rating 2.2 kW Replaced Catalog Number 3RV1011-1DA25 Returnable Y Series 3RV2 Standard CE / UL / CSA / CCC Standards CCC CertifiedCSA CertifiedUL ListedEAC ApprovedEX ATEXIECEx CertifiedCE CertifiedVDE ApprovedRoHS CompliantABS ApprovedBureau Veritas CertifiedLloyd's RegisteredPRS CertifiedRINA CertifiedRMRS ApprovedDNV-GL ApprovedEN 60715 Sub Brand Sirius Temperature Rating -20 to 60 °C Trip Range 2.2 to 3.2 A, 42 A Type 3RV2 circuit breaker UNSPSC 39121601 UPC 11 66264392390 UPC 12 662643923902 Width 2.0500 in Width [Metric] 5.2070 cm Wire Size 20 to 12 AWG Stock Status NONSTOCK Brand Siemens Manufacturer Siemens Amperage Rating 3.2 A Interrupt Rating 10 kA Trip Type Thermomagnetic Voltage Rating 690 VAC Used as Manual Motor Controller and in Group Installation MSP?s are UL approved as Self Protected Combination Motor Controllers Minimization of energy losses through optimization of the bimetal trip units Reduction of inherent power loss Less heating of the control cabinet Smaller control cabinet air conditioners can be used 3RV2 motor starter protectors/circuit breakers are suitable for operation in IT systems (IT networks) 550 W at 230 VAC, 1100 W at 400 VAC, 1500 W at 500 VAC, 2200 W at 690 VAC 100 kA at 240 VAC, 100 kA at 400 VAC, 100 kA at 500 VAC, 10 kA at 690 VAC 2.2 to 3.2 A thermal overload release, 42 A instantaneous overcurrent release
content loaded
content loaded
content loaded
content loaded
content loaded
- Attributes
- Documents & Resources
- Applications
- Features
- Substitute Products
| Alternate Catalog Number | 3RV2011-1DA25 |
| Application | Used as Manual Motor Controller and in Group Installation |
| ARRA Compliant | C |
| Auxiliary Contact Rating | 1NO-1NC |
| Buy American Compliant | C |
| Catalog Number | 3RV20111DA25 |
| Connection | spring-loaded terminals |
| Connection Type | Spring |
| Country of Origin | DE |
| Currency | USD |
| Dimensions | 106 mm H x 45 mm W x 97 mm D |
| Enclosure Type | IP20 |
| Environmental Conditions | 80 -50 C |
| EU RoHS Indicator | C |
| Frame | S00 |
| Frequency Rating | 50/60 Hz |
| Gross Volume Per Pack | 40.54 |
| Gross Volume UOM | in |
| Gross Weight Per Pack | 0.8140 lb |
| Gross Weight per Pack Metric | 0.37 |
| Gross Weight UOM Metric | kg |
| Harmonization Tariff Schedule Code | 8536304000 |
| Height | 4.1800 in |
| Height [Metric] | 10.6172 cm |
| Length | 4.7300 in |
| Length [Metric] | 12.0142 cm |
| Mounting Type | DIN Rail/Snap-On/Threaded |
| Number Of Poles | 3 |
| Operating Temperature | 60 to -20 °C |
| Phase | 3 |
| Power Rating | 2.2 kW |
| Replaced Catalog Number | 3RV1011-1DA25 |
| Returnable | Y |
| Series | 3RV2 |
| Standard | CE / UL / CSA / CCC |
| Standards | CCC CertifiedCSA CertifiedUL ListedEAC ApprovedEX ATEXIECEx CertifiedCE CertifiedVDE ApprovedRoHS CompliantABS ApprovedBureau Veritas CertifiedLloyd's RegisteredPRS CertifiedRINA CertifiedRMRS ApprovedDNV-GL ApprovedEN 60715 |
| Sub Brand | Sirius |
| Temperature Rating | -20 to 60 °C |
| Trip Range | 2.2 to 3.2 A, 42 A |
| Type | 3RV2 circuit breaker |
| UNSPSC | 39121601 |
| UPC 11 | 66264392390 |
| UPC 12 | 662643923902 |
| Width | 2.0500 in |
| Width [Metric] | 5.2070 cm |
| Wire Size | 20 to 12 AWG |
| Stock Status | NONSTOCK |
| Brand | Siemens |
| Manufacturer | Siemens |
| Amperage Rating | 3.2 A |
| Interrupt Rating | 10 kA |
| Trip Type | Thermomagnetic |
| Voltage Rating | 690 VAC |
| Used as Manual Motor Controller and in Group Installation |
| MSP?s are UL approved as Self Protected Combination Motor Controllers |
| Minimization of energy losses through optimization of the bimetal trip units |
| Reduction of inherent power loss |
| Less heating of the control cabinet |
| Smaller control cabinet air conditioners can be used |
| 3RV2 motor starter protectors/circuit breakers are suitable for operation in IT systems (IT networks) |
| 550 W at 230 VAC, 1100 W at 400 VAC, 1500 W at 500 VAC, 2200 W at 690 VAC |
| 100 kA at 240 VAC, 100 kA at 400 VAC, 100 kA at 500 VAC, 10 kA at 690 VAC |
| 2.2 to 3.2 A thermal overload release, 42 A instantaneous overcurrent release |