Weidmuller
Weidmuller ESX10-TB-101 Electric Circuit Breaker, 24 VDC, 10 A, 1 Poles, Electronic Trip
Weidmuller
Weidmuller ESX10-TB-101 Electric Circuit Breaker, 24 VDC, 10 A, 1 Poles, Electronic Trip
SKU1396664
MFGR #6720005330
Your Cost: $115.64/ea
Electronic circuit protection type ESX10-T is designed to ensure selective disconnection of 24 VDC load systems. 24 VDC power supplies, which are widely used in industry today, will shut down the output in the event of an overload with the result that one faulty load in the system can lead to complete disconnection of all loads. Through selective disconnection the ESX10-T responds much faster to overload or short circuit conditions than the switch-mode power supply. This is achieved by active current limitation. The ESX10-T limits the highest possible current to 1.3 to 1.8 times the selected rated current of the circuit protector. Thus it is possible to switch on capacitive loads of up to 20000 uF, but they are disconnected only in the event of an overload or short circuit. For optimal alignment with the characteristics of the application the current rating of the ESX10-T can be selected in fixed values from 0.5 to 12 A. Failure and status indication are provided by a multicolor LED and an integral short-circuit-proof status output or a relay signal contact. Remote operation is possible by means of a remote reset signal or a remote ON/OFF control signal. The manual ON/OFF button allows separate actuation and reset of individual load circuits.
Electronic circuit protection type ESX10-T is designed to ensure selective disconnection of 24 VDC load systems. 24 VDC power supplies, which are widely used in industry today, will shut down the output in the event of an overload with the result that one faulty load in the system can lead to complete disconnection of all loads. Through selective disconnection the ESX10-T responds much faster to overload or short circuit conditions than the switch-mode power supply. This is achieved by active current limitation. The ESX10-T limits the highest possible current to 1.3 to 1.8 times the selected rated current of the circuit protector. Thus it is possible to switch on capacitive loads of up to 20000 uF, but they are disconnected only in the event of an overload or short circuit. For optimal alignment with the characteristics of the application the current rating of the ESX10-T can be selected in fixed values from 0.5 to 12 A. Failure and status indication are provided by a multicolor LED and an integral short-circuit-proof status output or a relay signal contact. Remote operation is possible by means of a remote reset signal or a remote ON/OFF control signal. The manual ON/OFF button allows separate actuation and reset of individual load circuits.
Actuator Type Slide Switch Auxiliary Contact Rating SC/SO-SI Catalog Number 6720005330 Connection Type Threaded Dimensions 80 mm H x 12.5 mm W x 83 mm D Enclosure Type IP20 Gross Weight Per Pack 0.1400 lb Mounting Type DIN Rail Number Of Poles 1 Series ESX10-TB-101 Standards UL 2367File No E-306740UL 508File No E-322549UL 1604File No E-320024CSA Certified Temperature Rating 0 to 50 deg C Temperature Trip Range 100 ms to 3 sec Stock Status NONSTOCK Brand Weidmuller Manufacturer Weidmuller, USA Amperage Rating 10 A Trip Type Electronic Voltage Rating 24 VDC Selective load protection, electronic trip characteristics Active current limitation for safe connection of capacitive loads up-to 20000 micro-F and on overload/short circuit Reliable overload disconnection with 1.1 x in plus, even with long load lines or small cable cross sections Manual ON/OFF button (S1) Control input IN+ for remote ON/OFF signal (option) Electronic reset input RE (option) Clear status and failure indication through LED, status output SF or Si contact F Integral fail-safe element adjusted to current rating Width per unit only 12.5 mm Ease of wiring through busbar LINE+ and 0 V as well as signal bars and bridges Hazardous area approved - class 1 division 2, zone 2, ATEX zone 2 -20 to 70 deg C storage temperature Typically 20 to 30 mA closed current in on condition, depending on signal output Power-MOSFET switching load output (high side switch) Typically 3 sec trip time for electronic disconnection Internal temperature monitoring with electronic disconnection Typically 0.5 sec starting delay after every switch-on and after applying Ub Electronic disconnection of load output External free-wheeling diode recommended with inductive load 32 vdc maximum dielectric strength
content loaded
content loaded
content loaded
content loaded
- Attributes
- Documents & Resources
- Features
- Substitute Products
Actuator Type | Slide Switch |
Auxiliary Contact Rating | SC/SO-SI |
Catalog Number | 6720005330 |
Connection Type | Threaded |
Dimensions | 80 mm H x 12.5 mm W x 83 mm D |
Enclosure Type | IP20 |
Gross Weight Per Pack | 0.1400 lb |
Mounting Type | DIN Rail |
Number Of Poles | 1 |
Series | ESX10-TB-101 |
Standards | UL 2367File No E-306740UL 508File No E-322549UL 1604File No E-320024CSA Certified |
Temperature Rating | 0 to 50 deg C Temperature |
Trip Range | 100 ms to 3 sec |
Stock Status | NONSTOCK |
Brand | Weidmuller |
Manufacturer | Weidmuller, USA |
Amperage Rating | 10 A |
Trip Type | Electronic |
Voltage Rating | 24 VDC |
Selective load protection, electronic trip characteristics |
Active current limitation for safe connection of capacitive loads up-to 20000 micro-F and on overload/short circuit |
Reliable overload disconnection with 1.1 x in plus, even with long load lines or small cable cross sections |
Manual ON/OFF button (S1) |
Control input IN+ for remote ON/OFF signal (option) |
Electronic reset input RE (option) |
Clear status and failure indication through LED, status output SF or Si contact F |
Integral fail-safe element adjusted to current rating |
Width per unit only 12.5 mm |
Ease of wiring through busbar LINE+ and 0 V as well as signal bars and bridges |
Hazardous area approved - class 1 division 2, zone 2, ATEX zone 2 |
-20 to 70 deg C storage temperature |
Typically 20 to 30 mA closed current in on condition, depending on signal output |
Power-MOSFET switching load output (high side switch) |
Typically 3 sec trip time for electronic disconnection |
Internal temperature monitoring with electronic disconnection |
Typically 0.5 sec starting delay after every switch-on and after applying Ub |
Electronic disconnection of load output |
External free-wheeling diode recommended with inductive load |
32 vdc maximum dielectric strength |