The ACT20X-HDI-SDO/2HDI-2SNO RNO/RNC isolating switch amplifiers are specially designed for recording NAMUR sensor signals and digital switching signals which originate from Ex zone 0. Switching relays, optionally available with NO/NC contacts, transfer output signals to the safe zone. Integrated alarm contacts issue an alert in the event of a malfunction, this makes troubleshooting easier and increases system availability. The rail mounted disconnect-switch amplifiers are optionally available in one-/two-channel versions. With 11 mm W per channel, the devices need little space in the electrical cabinet.
The ACT20X-HDI-SDO/2HDI-2SNO RNO/RNC isolating switch amplifiers are specially designed for recording NAMUR sensor signals and digital switching signals which originate from Ex zone 0. Switching relays, optionally available with NO/NC contacts, transfer output signals to the safe zone. Integrated alarm contacts issue an alert in the event of a malfunction, this makes troubleshooting easier and increases system availability. The rail mounted disconnect-switch amplifiers are optionally available in one-/two-channel versions. With 11 mm W per channel, the devices need little space in the electrical cabinet.
Catalog Number 8965370000 Color Screw Terminal Connection Type Screw Country of Origin DK Dimensions 4.614 in H x 0.886 in W x 4.472 in D Gross Weight Per Pack 190.0000 lb Mounting Type DIN Rail Returnable Returnable with 50% restock fee Specification 0 to 95% Non-Condensing RH, -20 to 85 deg C Standards cULus Listed, UL E-337701, ATEX, IEC Ex Certified, RoHS Compliant, FM Approved Temperature Rating -20 to 60 deg C Stock Status NONSTOCK Brand Weidmuller Manufacturer Weidmuller, USA Input Voltage 19.2/31.2 VDC Number of Channels 2 NAMUR sensor/switch Safe-output - relay NO contact configuration <20 Hz input frequency 1 kOhm input resistance Output signal in case of wire break - 6.5 mA (in case of wire break) Input sensor supply - 8 VDC/8 mA Trigger level low - <1.2 mA Pulse duration - >0.1 ms Trigger level high - >2.1 mA Input type - intrinsically safe circuit Switching frequency - 0.02 kHz Rated switching voltage - </=250 VAC/30 VDC (safe area), </=32 VAC/32 VDC (zone 2) Power rating - </=500 VA/60 W (safe area), </=16 VA/32 W (zone 2) Continuous current - </=2 A AC/DC (safe area, zone 2) Alarm function - line interruption at the input, short-circuit at input, no supply voltage, device error Nominal switching voltage - </=125 VAC/110 VDC (safe area), </=32 VAC/32 VDC (zone 2) Power rating - </=62.5 VA/32 W (safe area), </=16 VA/32 W (zone 2) Alarm output type - relay, 1 NC (voltage-free) Continuous current - </=0.5 A AC/0.3 A DC (safe zone), </=0.5 A AC/1 A DC (zone 2)
content loaded
content loaded
content loaded
content loaded
- Attributes
- Documents & Resources
- Features
- Substitute Products
Catalog Number | 8965370000 |
Color | Screw Terminal |
Connection Type | Screw |
Country of Origin | DK |
Dimensions | 4.614 in H x 0.886 in W x 4.472 in D |
Gross Weight Per Pack | 190.0000 lb |
Mounting Type | DIN Rail |
Returnable | Returnable with 50% restock fee |
Specification | 0 to 95% Non-Condensing RH, -20 to 85 deg C |
Standards | cULus Listed, UL E-337701, ATEX, IEC Ex Certified, RoHS Compliant, FM Approved |
Temperature Rating | -20 to 60 deg C |
Stock Status | NONSTOCK |
Brand | Weidmuller |
Manufacturer | Weidmuller, USA |
Input Voltage | 19.2/31.2 VDC |
Number of Channels | 2 |
NAMUR sensor/switch |
Safe-output - relay |
NO contact configuration |
<20 Hz input frequency |
1 kOhm input resistance |
Output signal in case of wire break - 6.5 mA (in case of wire break) |
Input sensor supply - 8 VDC/8 mA |
Trigger level low - <1.2 mA |
Pulse duration - >0.1 ms |
Trigger level high - >2.1 mA |
Input type - intrinsically safe circuit |
Switching frequency - 0.02 kHz |
Rated switching voltage - </=250 VAC/30 VDC (safe area), </=32 VAC/32 VDC (zone 2) |
Power rating - </=500 VA/60 W (safe area), </=16 VA/32 W (zone 2) |
Continuous current - </=2 A AC/DC (safe area, zone 2) |
Alarm function - line interruption at the input, short-circuit at input, no supply voltage, device error |
Nominal switching voltage - </=125 VAC/110 VDC (safe area), </=32 VAC/32 VDC (zone 2) |
Power rating - </=62.5 VA/32 W (safe area), </=16 VA/32 W (zone 2) |
Alarm output type - relay, 1 NC (voltage-free) |
Continuous current - </=0.5 A AC/0.3 A DC (safe zone), </=0.5 A AC/1 A DC (zone 2) |