Appleton® EYM75 Unilet® EY Series Explosion Proof Conduit Sealing Fitting, 3/4 in, Malleable Iron, Tri-Coated

Conduit Sealing Fittings
16762 MFG #: EYM75
Appleton®
38.78000 / ea
  • Country of Origin: MX
  • Dimensions: 4.71 in L x 1.38 in W
  • Series: EY Series
  • Standards/Approvals: Buy American Act|RoHS Compliant|UL 886, UL 1203, UL File No. E10444|CSA C22.2 No. 30, CSA 065181, Class I, Groups A, B, C, D, Class II, Groups E, F, G, Class III
  • Stock Status: Normally Stocked
  • Type: Dust-Ignitionproof Explosionproof Raintight
  • UOM: lb
  • Weight: 0.7000
  • Brand Name: Appleton®
  • Manufacturer: Appleton, Division of Emerson
  • Size: 3/4 in
  • suitable For Use With: IMC/Threaded Rigid Metallic Conduit
  • Material: Malleable Iron
  • Finish: Triple Coated
These sealing fittings minimizes the passage of gases and vapors and prevents the passage of flames from one portion of a conduit system to another. they prevent pressure piling the within conduit system and contain any explosion that occurs. The EY series is a close radius type for sealing vertical or horizontal conduit runs.
QTY
  • Applications
  • Features
For prevent passage of gases, vapors or flames from one portion of conduit system to another
Smooth, rounded integral bushing in each hub to protect conductor insulation
Accurately tapped, tapered NPT threads for tight, rigid joints and ground continuity
Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
Restrict any explosion to the sealed off enclosure
Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure
Required where cables which exceed rate of gas or vapor transmission permitted for seals are used in Class I, Division 2 locations
25% fill vertical and horizontal conduit sealing fittings for close turning radius
Chromate/epoxy powder coated/zinc electroplated finish
1.19 in turning radius
Female threaded x male threaded connection
25% fill vertical and horizontal conduit sealing fittings for close turning radius
Triple-Coat (Zinc Electroplate, Chromate And epoxy Powder Coat) finish
For preventing passage of gases, vapors or flames from one portion of conduit system to another; Required in Class I, Division 1 and 2 locations where 2 IN or larger conduit enters enclosure, fitting housing terminals, splices or taps; Required in Class I