Siemens 3RV2711-1DD10 Type 3RV2 Motor Protection Circuit Breaker, 690 VAC, 3.2 A, 10 kA Interrupt, 3 Poles

Motor Protection Circuit Breakers
663785 MFG #: 3RV27111DD10
Siemens
253.54000 / ea
  • Actuator: selector switch
  • Actuator Type: Selector Switch
  • Alternate Catalog Number: 3RV2711-1DD10
  • Application: For system protection
  • ARRA Compliant: C
  • Buy American Compliant: C
  • Catalog Number: 3RV27111DD10
  • Connection: screw-type terminals
  • Connection Type: Screw
  • Country of Origin: DE
  • Currency: USD
  • Dimensions: 97 mm L x 45 mm W x 144 mm H
  • Enclosure Type: IP20
  • Environmental Conditions: 80 -50 C
  • EU RoHS Indicator: C
  • Frame: S00
  • Frequency Rating: 50/60 Hz
  • Gross Volume Per Pack: 74.38
  • Gross Volume UOM: in
  • Gross Weight Per Pack: 0.8150 lb
  • Gross Weight per Pack Metric: 0.37
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8536304000
  • Height: 2.30 in
  • Height [Metric]: 5.8420 cm
  • Length: 7.70 in
  • Length [Metric]: 19.5580 cm
  • Mounting Type: DIN Rail
  • Operating Temperature: 60 to -20 °C
  • Phase: 3
  • Power Rating: 2.2 kW
  • Replaced Catalog Number: 3RV1721-1DD10
  • Returnable: Y
  • Standards: ARRA CompliantBuy American Act CompliantRoHS CompliantCE MarkedCSA C22.2 No. 5-02UL 489
  • Sub Brand: Sirius
  • Temperature Rating: -20 to 60 °C
  • Trip Range: 3.2/42
  • Type: Type 3RV2
  • UNSPSC: 39121601
  • UPC 11: 66264392278
  • UPC 12: 662643922783
  • Width: 4.20 in
  • Width [Metric]: 10.6680 cm
  • Wire Size: 14 AWG
  • Stock Status: NORMALLY STOCKED
  • Brand: Siemens
  • Manufacturer: Siemens
  • Amperage Rating: 3.2 A
  • Interrupt Rating: 10 kA
  • Trip Type: Thermal Magnetic
  • Voltage Rating: 690 VAC
  • Number Of Poles: 3
Siemens 3RV27111DD10 TMCB UL489 S00 3.2A SCREW
QTY
  • Applications
  • Features
For system protection
Can optionally be fed from the top or from below
Screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Standard switch capacity
(2) 14 AWG wire
-50 to 80 deg C environmental conditions
Class 10 trip
100000 cycles switching
Can optionally be fed from the top or from below
3.2 A thermal overload release, 42 A instantaneous overcurrent release
Without auxiliary switch